153
-
'12 • PAC-T-173
Limitation on unit and piping installation - triple.
Descriptions
Marks appearing in the drawing
Models for outdoor unit
Dimensional limitations
Triple type A
> =
Triple type B
One-way pipe length
140
< =
100m
L + L1 + L2 + L3
L + La + L1 + L2 + L3
1
Main pipe length
140
< =
100m
L
L
One-way pipe length first branching point to indoor units
between
140
< =
30m
L1,
L2,
L3
L1
1
One-way pipe length between first branching point from and
second branching point
140
< =
5m
La
One-way pipe length first branching point and indoor units
140
< =
27m
La + L2,
La + L3
1
Piping length difference among piping to indoor units from first branch
<
3m
L1 - L2,
L1 - L3,
L2 - L3
( not possible )
3m
< =
< =
10m
( not possible )
L1 - (La + L2),
L1 - (La + L3)
1
One-way pipe length difference from second branching point to indoor units
< =
10m
L2 - L3
Elevation difference between indoor and outdoor
When the outdoor unit is positioned higher
< =
30m
HH
When the outdoor unit is positioned lower
< =
15m
Elevation difference among indoor units
< =
0.5m
h1,
h2,
h3
h1,
h2,
h3
Triple type A
H
L1
L2
L3
h1
h2
h3
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
L (riser)
L (riser)
Triple type B
H
L1
L2
L3
h1
h3
h2
La
Second branch
First branch
Indoor unit
Indoor unit
Outdoor unit
Model for
outdoor units
Triple type A
T
riple type B
Branch
piping
First branch
Second branch
140
DIS-TA1
DIS-WA1
DIS-WA1
Branch piping set (option)
(1) A riser pipe must be part of the main.
A branching pipe set should be installed horizontally at point as close to an indoor unit as possible.
(2) Reduce refrigerant amount by 1.0kg from the factory charge when refrigerant piping is shorter than 3m.
ޓޓޓ
1
Install
the
indoor
units
so
that
L
+
L
1
becomes
the
longest
one-way pipe.
Keep the pipe length difference
between L1 and (La + L2)
or (La + L3) within 10m.
B
PJF000Z195
Summary of Contents for FDC Series
Page 95: ... 94 12 PAC T 173 Models FDT100VF 125VF 140VF H H H H H C B A F G D G PJF000Z285 ...
Page 98: ... 97 12 PAC T 173 Models FDEN60VF 71VF C 2 C 1 A B A B D C 1 C 2 C 1 C 2 E G F B PFA003Z817 ...
Page 113: ... 112 12 PAC T 173 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 278: ... 277 12 PAC T 173 ー K ...
Page 346: ... 345 12 PAC T 173 Power PCB 1BSU OVNCFS 4GRNCEG VJG 2 ...
Page 518: ... 517 12 PAC T 173 3 5 SUPER LINK E BOARD SC ADNA E F SL2NA E and SL3N AE BE to control ...
Page 519: ... 518 12 PAC T 173 ...