'12 • PAC-T-173
(8) Effective range of cool/hot wind (Reference)
(a) FDT series
Guideline for ceiling height
Fan Speed Setting
Model
FDT40VF50VF60VF
FDT71VF
FDT100VF
FDT125VF,140VF
Hi
2.7m
3.0m
3.2m
3.6m
PHi
3.5m
3.8m
4.3m
4.5m
Notes (1) If the ceiling height is over 3m, please consider to add circulators.
This table shows reference values in case of four outlet.
If you shut some outlets, they are different.
Fan speed setting can be changed by using a wired remote controller.
(b) FDEN series
Model
Effective range
FDEN40VF, 50VF
7.5m
FDEN60VF, 71VF
8.0m
FDEN100VF, 125VF, 140VF
9.0m
[Conditions]
1.
+HLJKWRIXQLW±PDERYHÀRRUOHYHO
2.
Fan speed : Hi
3.
Location: Free space without obstacles
4.
7KHHIIHFWLYHUDQJHPHDQVWKHKRUL]RQWDOGLVWDQFHIRUWKHZLQGWRUHDFKWKHÀRRU
5.
Wind speed at the effective range: 0.5 m/s
(c) FDF series
Model
Effective range
FDF71VD
5m
FDF100VD, 125VD, 140VD
8m
[Conditions]
1.
Fan speed : Hi
2.
Location: Free space without obstacles
3.
7KHHIIHFWLYHUDQJHPHDQVWKHKRUL]RQWDOGLVWDQFHIRUWKHZLQGWRUHDFKWKHÀRRU
4.
Wind speed at the effective range: 0.5 m/s
Summary of Contents for FDC Series
Page 95: ... 94 12 PAC T 173 Models FDT100VF 125VF 140VF H H H H H C B A F G D G PJF000Z285 ...
Page 98: ... 97 12 PAC T 173 Models FDEN60VF 71VF C 2 C 1 A B A B D C 1 C 2 C 1 C 2 E G F B PFA003Z817 ...
Page 113: ... 112 12 PAC T 173 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 278: ... 277 12 PAC T 173 ー K ...
Page 346: ... 345 12 PAC T 173 Power PCB 1BSU OVNCFS 4GRNCEG VJG 2 ...
Page 518: ... 517 12 PAC T 173 3 5 SUPER LINK E BOARD SC ADNA E F SL2NA E and SL3N AE BE to control ...
Page 519: ... 518 12 PAC T 173 ...