248
-
'12 • PAC-T-173
Ԛ
Function Setting by Remote Controller (Continued)
ԛ
Trial operation
[Flow of function setting]
Start
: While indoor unit do not operate, press “ ” (SET) and “ ” (MODE) button for 3 seconds at the same time.
Finalize : Press “ ” (SET) button.
Reset
: Press “ ” (RESET) button.
Select
: Press button.
End
: Press button.
It is possible to finish above setting on the way, and unfinished change of setting is unavailable.
“ ” : Initial settings
“ ” : Automatic criterion
As for detail, refer to the installation manual of remote controller.
Only when plural indoor units are connected
Indoor No. selection
01
02
When you use at 50Hz area
When you use at 60Hz area
Automatic operation is impossible
(Remote controller function)
Temperature setting button is not working
02
03
03
04
04
05
05
06
06
07
07
08
09
08
10
09
11
10
12
11
13
12
13
14
14
15
16
15
17
16
18
19
Make permission/prohibition control of function be in effect.
Function
setting
Mode button is not working
On/Off button is not working
Fan speed button is not working
Louver button is not working
Timer button is not working
Heating preparation indication should not be indicated.
The filter sign is indicated after running for 180 hours.
The filter sign is indicated after running for 600 hours.
The filter sign is indicated after running for 1000 hours.
The filter sign is indicated after running for 1000 hours, then it will be stopped by compulsion after 24 hours.
If to change the indoor function "04 ",
The remote control function "14 " should be changed accordingly.
Select the louver stop position in four.
The louver can stop at any positon.
With the VRF series, it is used to stop all indoor units connected with the same outdoor unit immediately.
When stop signal is inputed from remote on-off terminal "CNT-6", all indoor units are stopped immediately.
To be reset for pro3.0°C increase in temperature during heating.
To be reset for pro2.0°C increase in temperature during heating.
To be reset for pro1.0°C increase in temperature during heating.
To be reset pro2.0°C increase in return air temperature of indoor unit.
To be reset pro1.5°C increase in return air temperature of indoor unit.
To be reset pro1.0°C increase in return air temperature of indoor unit.
To be reset producing -1.0°C increase in return air temperature of indoor unit.
To be reset producing -1.5°C increase in return air temperature of indoor unit.
To be reset producing -2.0°C increase in return air temperature of indoor unit.
When heating thermostat is off, to be operated with low fan speed. (or with ultra low fan speed in case of some models)
When heating thermostat is off, to be operated with set fan speed.
When heating thermostat is off, to be operated intermittently.
When heating thermostat is off, the fan stops.
When the remote thermistor is working, "FAN OFF" is set automatically.
Do not set when the indoor unit's thermistor is working.
Drain pump is on during cooling and dry.
Drain pump is on during cooling, dry and heating.
Drain pump is on during cooling, dry, heating and fan.
Drain pump is on during cooling, dry and fan.
After cooling is stopped the fan does not perform extra operation.
After cooling is stopped the fan perform extra operation for half an hour.
After cooling is stopped the fan perform extra operation for an hour.
After cooling is stopped the fan perform extra operation for six hours.
After heating is stopped or heating thermostat is off, the fan does not perform extra operation.
After heating is stopped or heating thermostat is off,the fan perform extra operation for half an hour.
After heating is stopped or heating thermostat is off,the fan perform extra operation for two hours.
After heating is stopped or heating thermostat is off, the fan perform extra operation for six hours.
During heating is stopped or heating thermostat is off, the fan perform intermittent operation
for five minutes after twenty minutes' off with low airflow.
During heating is stopped or heating thermostat is off, the fan perform intermittent operation
for five minutes after five minutes' off with low airflow.
Items marked with
ڎ
are not available on the floor standing FDF.
Do not change the initial setting
Working only with the single split series.
To control frost prevention, the indoor fan tap is raised.
Change of indoor heat exchanger temperature to start frost prevention control.
Function
setting
Remote thermistor is not working.
Remote thermistor is working.
Remote thermistor is working, and to be set for pro3.0°C increase in temperature.
Remote thermistor is working, and to be set for pro2.0°C increase in temperature.
Remote thermistor is working, and to be set for pro1.0°C increase in temperature.
Remote thermistor is working, and to be set for producing -1.0°C increase in temperature.
Remote thermistor is working, and to be set for producing -2.0°C increase in temperature.
Remote thermistor is working, and to be set for producing -3.0°C increase in temperature.
If you want to change the remote control function "14 ",
You must change the indoor function "04 " accordingly.
You can select the louver stop position in the four.
The louver can stop at any position.
Temperature indication is by degree C
Temperature indication is by degree F
If to change re-set with other indoor
unit, push AIRCON NO.
button, and indoor selection indication
(for example: I/U 000) is set back.
Consult the technical data etc. for each control details
Record and save the
setting
(Note3)
(Note2)
Connect the Single split series and the VRF series to the indoor board CNT and indoor board CND respectively. If a
ventilation device is connected, been geared with the motion of indoor device, the ventilation device is operated/stopped.
By connecting the ventilation device with the Single split series device to indoor board CNT, the VRF series device to
CND, you can operate/stop the ventilation device independently by the handling of ventilation button.
If you change the range of set temperature, the indication of set temperature will vary following the control.
If you change the range of set temperature, the indication of set temperature will not vary following the control, and
keep the set temperature.
If you input into the indoor printed circuit board CNT from outside, the indoor device will be operated independently
following the input from outside.
If you input into indoor printed circuit board CNT from outside, All units which share the same one remote control
network work following the input from outside.
During air-conditioner stopping push
(SET) + (MODE) button
simultaneously for 3 seconds
In normal working indication, indoor unit temperature is indicated instead of airflow.
(Only the master remote control can be indicated. )
(Indoor unit function)
Airflow of fan becomes the three speed of - - or - - - .
Airflow of fan becomes the two speed of - .
Airflow of fan becomes the two speed of - .
Airflow of fan is fixed at one speed.
ڎ
ڎ
ڎ
ڎ
ڎ
ڎ
ڎ
ON/OFF button (finished)
The method of trial cooling operation
Operate the remote control unit as follows.
1. Starting a cooling test run.
Ԙ
Start the system by pressing the button.
ԙ
Select “ (Cool)” with the (MODE) button.
Ԛ
Press the
TEST
button for 3 seconds or longer.
The screen display will switch to: “
”
ԛ
When the (SET) button is pressed while “
” is indicated, a cooling test
run will start.
The screen display will switch to “ ”.
2. Ending a cooling test run.
Pressing the button, the (TEMP) button or (MODE) button will end a
cooling test run. (Cooling test run will end after 30 minutes pass.)
“ ” shown on the screen will go off.
Summary of Contents for FDC Series
Page 95: ... 94 12 PAC T 173 Models FDT100VF 125VF 140VF H H H H H C B A F G D G PJF000Z285 ...
Page 98: ... 97 12 PAC T 173 Models FDEN60VF 71VF C 2 C 1 A B A B D C 1 C 2 C 1 C 2 E G F B PFA003Z817 ...
Page 113: ... 112 12 PAC T 173 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 278: ... 277 12 PAC T 173 ー K ...
Page 346: ... 345 12 PAC T 173 Power PCB 1BSU OVNCFS 4GRNCEG VJG 2 ...
Page 518: ... 517 12 PAC T 173 3 5 SUPER LINK E BOARD SC ADNA E F SL2NA E and SL3N AE BE to control ...
Page 519: ... 518 12 PAC T 173 ...