262
-
'12 • PAC-T-173
If the hole is cut too large, moisture, dust or insects may enter.
Seal gaps with putty or the like.
④
Fix the bottom R/C case on a
flat surface with wood screws.
⑤
In case of the upper center,
p a s s t h e w i r i n g b e h i n d
the bottom case. (Hatched
section)
⑥
Fix wires such that the wires
will run around the terminal
screw of the top case of R/C.
⑦
Install the top case with care
not to pinch wires of R/C.
120mm
(for retrieving
wire from
upper left)
8
190mm
(for retrieving wire
from upper center)
Main-Sub setting for use of two or more R/Cs
Up to two units of R/C can be used at the maximum for 1 indoor unit or 1 group.
One is main R/C and the other is sub R/C.
Operating range is different depending on the main or sub R/C.
R/C function
Main
Sub
Run/Stop, setting temperature, fan speed and flap
direction operations
○
○
High power and energy-saving operations
○
○
Energy-saving setting
○
−
R/C sensor
○
−
Test run menu operation
○
−
Room temperature range setting
○
−
Indoor unit settings
○
−
Individual flap control
○
−
Operation data display
○
−
Error history display
○
○
Indoor unit
R/C cable (No polarity)
R/C
“Main”
R/C
“Sub”
X Y
X Y
X Y
Set the “Main” and “Sub” as described at Section 7
of installtion manual attached to the remote control.
Main/Sub setting when more than one remote control are used
Summary of Contents for FDC Series
Page 95: ... 94 12 PAC T 173 Models FDT100VF 125VF 140VF H H H H H C B A F G D G PJF000Z285 ...
Page 98: ... 97 12 PAC T 173 Models FDEN60VF 71VF C 2 C 1 A B A B D C 1 C 2 C 1 C 2 E G F B PFA003Z817 ...
Page 113: ... 112 12 PAC T 173 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 278: ... 277 12 PAC T 173 ー K ...
Page 346: ... 345 12 PAC T 173 Power PCB 1BSU OVNCFS 4GRNCEG VJG 2 ...
Page 518: ... 517 12 PAC T 173 3 5 SUPER LINK E BOARD SC ADNA E F SL2NA E and SL3N AE BE to control ...
Page 519: ... 518 12 PAC T 173 ...