314
-
'12 • PAC-T-173
1.11.4 Operation control function by the outdoor controller
(
Ⅰ
) Models SRC40-60
(1)
Defrosting operation
(a)
Starting conditions (Defrosting operation can be started only when all of the following conditions are met.)
1)
After start of heating operation
When it elapsed 35 minutes. (Accumulated compressor operation time)
2)
After end of defrosting operation
When it elapsed 35 minutes. (Accumulated compressor operation time)
3)
Outdoor heat exchanger sensor (TH1) temperature
When the temperature has been below
−
5ºC for 3 minutes continuously.
4)
The difference between the outdoor air sensor temperature and the outdoor heat exchanger sensor temperature
f
The outdoor air temperature
≧ −
2ºC : 7ºC or higher
f
−
15ºC
≦
The outdoor air temperature
< −
2ºC : 4/15 × The outdoor air tempe 7ºC or higher
f
The outdoor air temperature
< −
15ºC :
−
5ºC or higher
5)
During continuous compressor operation
In addition, when the speed command from the indoor controller of the indoor unit during heating operation has counted
0 rps 10 times or more and all conditions of a), b), c) and e) above and the outdoor air temperature is 3ºC or less are
VDWLV¿HGQRWHWKDWZKHQWKHWHPSHUDWXUHIRURXWGRRUKHDWH[FKDQJHULV
−
5ºC or less: 62 rps or more,
−
4ºC or less: less than 62 rps), defrost operation is started.
(b)
Ending conditions (Operation returns to the heating cycle when either one of the following is met.)
1)
Outdoor heat exchanger sensor (TH1) temperature:
10ºC or higher
2)
&RQWLQXHGRSHUDWLRQWLPHRIGHIURVWLQJĺ)RUPRUHWKDQPLQXWHV
Max. 18 minutes
Heating operation
¡
Defrast operation
̪
Depends on an operation condition, the time can be longer than 7 minutes.
2~7 minutes
̪
Hot keep operation
-20
-20
-15
-10
-5
0
5
10
-15
-10
-5
0
Outdoor air temperature (
㷄
)
Outdoor heat exchanger temperature (
㷄
)
Defrost operation
start
Defrost operation start temperature
Summary of Contents for FDC Series
Page 95: ... 94 12 PAC T 173 Models FDT100VF 125VF 140VF H H H H H C B A F G D G PJF000Z285 ...
Page 98: ... 97 12 PAC T 173 Models FDEN60VF 71VF C 2 C 1 A B A B D C 1 C 2 C 1 C 2 E G F B PFA003Z817 ...
Page 113: ... 112 12 PAC T 173 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 278: ... 277 12 PAC T 173 ー K ...
Page 346: ... 345 12 PAC T 173 Power PCB 1BSU OVNCFS 4GRNCEG VJG 2 ...
Page 518: ... 517 12 PAC T 173 3 5 SUPER LINK E BOARD SC ADNA E F SL2NA E and SL3N AE BE to control ...
Page 519: ... 518 12 PAC T 173 ...