316
-
'12 • PAC-T-173
C
D
A
B
OFF
Upper limit 60 rps
Lower limit 45 rps
ON
ON
Upper limit 75 rps
Lower limit 35 rps
Outdoor air temperature (°C)
First time
Since the seconds
times
9
A
Outdoor air temp. (˚C)
B
C
D
11
22
25
16
19
25
f
Values of A, B, C, D
(c)
Reset conditions:
:KHQHLWKHURIWKHIROORZLQJFRQGLWLRQLVVDWLV¿HG
1)
The outdoor air temperature (TH2) is D ºC or higher.
2)
The compressor command speed is 0 rps.
(5)
Heating high pressure control
(a)
Purpose:
Prevents anomalous high pressure operation during heating.
(b)
Detector:
Indoor heat exchanger thermistor (Th
I
-R)
(c)
Detail of operation:
A
B
C
D
Indoor heat exchanger temperature(°C)
4rps
(1)
8rps
(2)
8rps
(2)
4rps
(1)
0rps
After lapse of 10 sec. or over
(3)
After lapse of 10 sec. or over
(3)
After lapse of 10 sec. or over
(3)
lower limit
speed 35rps
(Example) Fuzzy
Notes (1) When the indoor heat exchanger temperature is in the range of B~C ºC, the speed is reduced by 4 rps at each 10seconds.
:KHQWKHLQGRRUKHDWH[FKDQJHUWHPSHUDWXUHLVLQWKHUDQJHRI&a'&WKHVSHHGLVUHGXFHGE\USVDWHDFKVHFRQGV:KHQWKHWHPSHUDWXUHLV'&
or higher continues for 1 minute, the compressor is stopped.
(3) When the indoor heat exchanger temperature is in the range of A~B ºC, if the compressor command speed is been maintained and the operation has contin-
ued for more than 10 seconds at the same speed, it returns to the normal heating operation.
(4) Indoor blower retains the fan tap when it enters in the high pressure control. Outdoor blower is operated in accordance with the speed.
f
Temperature list
A
B
C
D
RPSmin < 50
45
52
54.5
61
50 <
= RPSmin < 115
45
52
57
61
115 <
= RPSmin < 120
45 ~ 43
52 ~ 50
57
61 ~ 59
120 <
= RPSmin
43
50
55
59
Unit : ºC
Note (1) RPSmin: The lower one between the outdoor speed and the compressor command speed
(6)
Heating overload protective control
(a)
Indoor unit side
1) Operating conditions :
2) Detail of operation :
3) Reset conditions :
H
H
ާޓޓޓޓޓޓޓޓި
Summary of Contents for FDC Series
Page 95: ... 94 12 PAC T 173 Models FDT100VF 125VF 140VF H H H H H C B A F G D G PJF000Z285 ...
Page 98: ... 97 12 PAC T 173 Models FDEN60VF 71VF C 2 C 1 A B A B D C 1 C 2 C 1 C 2 E G F B PFA003Z817 ...
Page 113: ... 112 12 PAC T 173 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 278: ... 277 12 PAC T 173 ー K ...
Page 346: ... 345 12 PAC T 173 Power PCB 1BSU OVNCFS 4GRNCEG VJG 2 ...
Page 518: ... 517 12 PAC T 173 3 5 SUPER LINK E BOARD SC ADNA E F SL2NA E and SL3N AE BE to control ...
Page 519: ... 518 12 PAC T 173 ...