321
-
'12 • PAC-T-173
(3)
Compressor soft start control
(a)
Compressor protection start I
[Control condition]
Normally, the compressor operation frequency is raised in this start pattern.
[Control contents]
1)
Starts with the compressor’s target frequency at
A
rps.
However, when the ambient air temperature (Tho-A) is 35°C or higher during cooling/
dehumidifying or the indoor return air temperature (Th
I
-A) is 25°C or higher during heating, it
starts at
C
rps.
2)
At 30 seconds after the start of compressor, its target frequency changes to
B
rps and the
compressor is operated for 2 - 4 minutes with its operation frequency fixed at
B
rps.
Model
Operation mode
A
rps
B
rps
C
rps
71
Cooling/Dehumidifying
42
42
40
Heating
62
62
40
100
Cooling/Dehumidifying
55
55
30
Heating
55
55
30
125, 140
Cooling/Dehumidifying
45
45
25
Heating
45
45
25
(b)
Compressor protection start III
[Control condition]
Number of compressor starts is only 1 counted after the power supply breaker ON.
[Control contents]
Operates by selecting one of following start patterns according to the operation mode and the
outdoor air temperature (Tho-A).
1) Low frequency operation control during cooling/dehumidifying
[Control condition] Upon establishing the conditions of compressor protection start III, the low frequency
operation control is performed during cooling/dehumidifying.
[Control contents]
a) Starts with the compressor’s target frequency at
A
rps. When the outdoor air temperature
(Tho-A) is 35°C or higher, it starts at
C
rps.
b)
At 30 seconds after the compressor start, the compressor’s target frequency is changed to
B
rps and the compressor’s operation frequency is fixed for 10 minutes.
Model
Operation mode
A
rps
B
rps
C
rps
71
Cooling/Dehumidifying
42
42
40
100
Cooling/Dehumidifying
55
55
30
125, 140
Cooling/Dehumidifying
45
45
25
2) Low frequency operation control during heating
[Control condition] When the conditions of compressor protection start III are established and one of following conditions
a) is satisfied, the low number of revolutions operation control is performed during heating.
a) At 30 minutes or more after turning the power supply breaker on
[Control contents]
a) Starts the compressor with its target frequency at
A
rps. However, when the indoor unit
return air temperature (Th
I
-A) is 25°C or higher, it start at
C
rps.
b) At 30 seconds after the start of compressor, the compressor’s target frequency is changed to
B
rps and the compressor’s operation frequency is fixed for 10 minutes.
Model
Operation mode
A
rps
B
rps
C
rps
71
Heating
42
42
40
100
Heating
55
55
30
125, 140
Heating
45
45
25
Summary of Contents for FDC Series
Page 95: ... 94 12 PAC T 173 Models FDT100VF 125VF 140VF H H H H H C B A F G D G PJF000Z285 ...
Page 98: ... 97 12 PAC T 173 Models FDEN60VF 71VF C 2 C 1 A B A B D C 1 C 2 C 1 C 2 E G F B PFA003Z817 ...
Page 113: ... 112 12 PAC T 173 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 278: ... 277 12 PAC T 173 ー K ...
Page 346: ... 345 12 PAC T 173 Power PCB 1BSU OVNCFS 4GRNCEG VJG 2 ...
Page 518: ... 517 12 PAC T 173 3 5 SUPER LINK E BOARD SC ADNA E F SL2NA E and SL3N AE BE to control ...
Page 519: ... 518 12 PAC T 173 ...