330
-
'12 • PAC-T-173
(10) Base heater ON/OFF output control (optional)
1)
Base heater ON conditions
When all of following conditions are met, the base heater is turned ON.
・
Outdoor air temperature (detected with Tho-A) is 3ºC or lower.
・
In the heating mode
・
When the compressor is turned ON
2)
Base heater OFF conditions
:KHQHLWKHURQHRIIROORZLQJFRQGLWLRQVLVPHWWKHEDVHKHDWHULVWXUQHG2))
・
Outdoor air temperature (detected with Tho-A) is 5ºC or higher.
・
When the compressor stop has been detected for 30 minutes continuously
・
In the cooling or dehumidifying mode
Base heater ON
%DVHKHDWHU2))
Outdoor air temperature (ºC) [Tho-A]
5
3