333
-
'12 • PAC-T-173
(ii)
Outdoor unit
1) SRC40-60
Remote controller
Indoor control PCB
Outdoor control PCB
Location of trouble
Description of trouble
Repair method
Reference
page
Error code
Red LED
Red LED
Green
LED
Red LED
Keeps
flashing
6WD\V2))
Keeps
flashing
2 times flash
Installation, operation status • Higher outdoor heat exchanger temperature
Repair
397
Outdoor heat exchanger
temperature sensor
• Defective outdoor heat exchanger temperature sensor
Replacement, repair
of temperature
sensor
Outdoor control PCB
*• Defective outdoor control PCB (Defective temperature sensor input
circuit)?
Replacement of
PCB
6WD\V2))
Keeps
flashing
5 times flash
Installation, operation status • Higher discharge temperature
Repair
399
Discharge pipe temperature
sensor
• Defective discharge pipe temperature sensor
Replacement, repair
of temperature
sensor
Outdoor control PCB
*• Defective outdoor control PCB (Defective temperature sensor input
circuit)?
Replacement of
PCB
6WD\V2))
Keeps
flashing
WLPHVIODVK
Outdoor heat exchanger
temperature sensor
• Defective outdoor heat exchanger temperature sensor, broken wire or poor
connector connection
Replacement, repair
of temperature
sensor
400
Outdoor control PCB
*• Defective outdoor control PCB (Defective temperature sensor input
circuit)?
Replacement of
PCB
6WD\V2))
Keeps
flashing
WLPHVIODVK
Outdoor air temperature
sensor
• Defective outdoor air temperature sensor, broken wire or poor connector
connection
Replacement, repair
of temperature
sensor
401
Outdoor control PCB
*• Defective outdoor control PCB (Defective temperature sensor input
circuit)?
Replacement of
PCB
6WD\V2))
Keeps
flashing
WLPHVIODVK
Discharge pipe temperature
sensor
• Defective discharge pipe temperature sensor, broken wire or poor connector
connection
Replacement, repair
of temperature
sensor
402
Outdoor control PCB
*• Defective outdoor control PCB (Defective temperature sensor input
circuit)?
Replacement of
PCB
6WD\V2))
Keeps
flashing
1 time flash
Outdoor control PCB,
compressor
• Current cut (Anomalous compressor over-current)
Replacement of
PCB
405
•
406
Installation, operation status • Service valve closing operation
Repair
6WD\V2))
Keeps
flashing
2 times flash
Outdoor control PCB
• Defective active filter
Repair
PCB replacement
6WD\V2))
Keeps
flashing
Keeps
flashing
)DQPRWRU
• Defective fan motor
Replacement
410
Outdoor control PCB
• Defective outdoor control PCB
6WD\V2))
Keeps
flashing
1 time flash
Power transistor error
(outdoor control PCB)
• Power transistor error
Replacement of
PCB
414
6WD\V2))
Keeps
flashing
2 times flash
Operation status
• Shortage in refrigerant quantity
Repair
Installation status
• Service valve closing operation
Service valve
opening check
6WD\V2))
Keeps
flashing
3 times flash
• Overload operation
• Overcharge
• Compressor locking
• Current safe stop
Replacement
420
6WD\V2))
Keeps
flashing
2 times flash
Compressor, outdoor control
PCB
• Anomalous compressor startup
Replacement
421
6WD\V2))
Keeps
flashing
7 times flash
Compressor
• Anomalous compressor rotor lock
Replacement
424
1RWHPDUNLQWKH'HVFULSWLRQRIWURXEOHPHDQVWKDWLQRUGLQDU\GLDJQRVLVLWFDQQRWLGHQWLI\WKHFDXVHGH¿QLWHO\DQGLIWKHWURXEOHLVUHSDLUHGE\UHSODFLQJWKH
part, it is judged consequently that the replaced part was defective.
Summary of Contents for FDC Series
Page 95: ... 94 12 PAC T 173 Models FDT100VF 125VF 140VF H H H H H C B A F G D G PJF000Z285 ...
Page 98: ... 97 12 PAC T 173 Models FDEN60VF 71VF C 2 C 1 A B A B D C 1 C 2 C 1 C 2 E G F B PFA003Z817 ...
Page 113: ... 112 12 PAC T 173 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 278: ... 277 12 PAC T 173 ー K ...
Page 346: ... 345 12 PAC T 173 Power PCB 1BSU OVNCFS 4GRNCEG VJG 2 ...
Page 518: ... 517 12 PAC T 173 3 5 SUPER LINK E BOARD SC ADNA E F SL2NA E and SL3N AE BE to control ...
Page 519: ... 518 12 PAC T 173 ...