-
337
-
'12 • PAC-T-173
N
Error log and reset
Error indicator
Memorized error log
Reset
Remote controller display
• Higher priority error is memorized.
6WRSWKHXQLWE\SUHVVLQJWKH212))
switch of remote controller.
• If the unit has recovered from anomaly, it
can be operated.
Red LED on indoor control PCB
• Not memorized.
Red LED on outdoor control PCB
• Memorizes a mode of higher priority.
N
Resetting the error log
• Resetting the memorized error log in the remote controller
Holding down “CHECK” button, press “TIMER” button to reset the error log memorized in the remote controller.
• Resetting the memorized error log
The remote controller transmits error log erase command to the indoor unit when “VENTI” button is pressed while
holding down “CHECK” button.
Receiving the command, the indoor unit erase the log and answer the status of no error.
(2)
Troubleshooting procedure
When any trouble has occurred, inspect as follows. Details of respective inspection method will be described on later pages.
Trouble
Confirmation
of power
supply
(Indoor/
outdoor unit)
Confirmation of
remote controller and
LEDs on the PCB
of indoor unit and
outdoor unit (Indoor/
outdoor unit, remote
controller)
Check of the anomalous
operation data on the
remote controller
Inspection
of the unit/
controller
Replacement/
repair of
faulty part,
test run,
adjustment
(3)
Troubleshooting at the indoor unit
(a)
FDT, FDTC, FDEN, FDU, FDUM, FDF series
:LWKWKHWURXEOHVKRRWLQJ¿QGRXWDQ\GHIHFWLYHSDUWE\FKHFNLQJWKHYROWDJH$&'&UHVLVWDQFHHWFDWUHVSHFWLYHFRQQHFWRUV
at around the indoor PCB, according to the inspection display or operation status of unit (the compressor does not run, fan does
not run, the 4-way valve does not switch, etc.), and replace or repair in the unit of following part.
(i)
Replacement part related to indoor PCB’s
Control PCB, power supply PCB, temperature thermistor (return air, indoor heat exchanger), remote controller switch,
limit switch, transformer and fuse
Note (1) With regard to parts of high voltage circuits and refrigeration cycle, judge it according to ordinary inspection methods.
(ii)
Instruction of how to replace indoor control PCB
٨
Read the "SAFETY PRECAUTIONS" carefully first of all and then strictly follow it during the replacement in order to protect yourself.
٨
The precautionary items mentioned below are distinguished into two levels, WARNING and CAUTION.
Both mentions the important items to protect your health and safety so strictly follow them by any means.
WARNING
Wrong installation would cause serious consequences such as injuries or death.
CAUTION
Wrong installation might cause serious consequences depending on circumstances.
٨
After completing the replacement, do commissioning to confirm there are no anomaly.
٨
Replacement should be performed by the specialist.
If you replace the PCB by yourself, it may lead to serious trouble such as electric shock or fire.
٨
Replace the PCB correctly according to these instructions.
Improper replacement may cause electric shock or fire.
٨
Shut off the power before electrical wiring work.
Replacement during the applying the current would cause the electric shock, unit failure or improper running.
It would cause the damage of connected equipment such as fan motor,etc.
٨
Fasten the wiring to the terminal securely, and hold the cable securely so as not to apply unexpected stress on the terminal.
Loose connections or hold could result in abnormal heat generation or fire.
٨
Check the connection of wiring to PCB correctly before turning on the power, after replacement.
Defectiveness of replacement may cause electric shock or fire.
٨
In connecting connector onto the PCB, connect not to deform the PCB. It may cause breakage or malfunction.
٨
Insert connecter securely, and hook stopper. It may cause fire or improper running.
٨
Bundle the cables together so as not to be pinched or be tensioned. It may cause malfunction or electric shock for disconnection or deformation.
ޓޓޓޓޓޓޓޓޓ
CAUTION
SAFETY PRECAUTIONS
ޓޓޓޓޓޓޓޓޓޓ
WARNING
Summary of Contents for FDC Series
Page 95: ... 94 12 PAC T 173 Models FDT100VF 125VF 140VF H H H H H C B A F G D G PJF000Z285 ...
Page 98: ... 97 12 PAC T 173 Models FDEN60VF 71VF C 2 C 1 A B A B D C 1 C 2 C 1 C 2 E G F B PFA003Z817 ...
Page 113: ... 112 12 PAC T 173 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 278: ... 277 12 PAC T 173 ー K ...
Page 346: ... 345 12 PAC T 173 Power PCB 1BSU OVNCFS 4GRNCEG VJG 2 ...
Page 518: ... 517 12 PAC T 173 3 5 SUPER LINK E BOARD SC ADNA E F SL2NA E and SL3N AE BE to control ...
Page 519: ... 518 12 PAC T 173 ...