356
-
'12 • PAC-T-173
(b) In case of RC-EX1A remote controller
[Operating procedure]
On the TOP screen, touch the buttons in the order of “Menu”
©
“Next”
©
“Service & Maintenance”
©
“Service password”
©
“Set”
©
“Error display”
©
“Error history”.
When only one indoor unit is connected to the remote controller, followings will be displayed.
1. When there is any anomaly: “Loading. Wait a while” is displayed, followed by the operation data at the occurrence of anomaly.
Contents of display
・
Error code
・
Number and data item
2. When there is no anomaly: “No anomaly” is displayed, and this mode is terminated.
When two or more indoor units are connected to the remote controller, followings will be displayed.
1. When there is any anomaly: If the unit having anomaly is selected on the “Select IU” screen, “Loading. Wait a while” is
displayed, followed by the operation data at the occurrence of anomaly.
Contents of display
・
Indoor unit No.
・
Error code
・
Number and data item
2. When there is no anomaly: “No anomaly” is displayed, ant this mode is terminated.
Note (1) When the number of connected units cannot be shown in a page, select “Next”.
If you press [RUN/STOP] button, the display returns to the TOP screen.
◎
If you touch “Back” button on the way of setting, the display returns to the last precious screen.
Note (1) When two remote controllers are used to control indoor units, the check of anomaly operation data can be made on the master remote controller only. (It
cannot be operated from the slave remote controller.)
Ŷ$QRPDO\RSHUDWLRQGDWD&RUUHVSRQGLQJGDWDPD\QRWEHSURYLGHGGHSHQGLQJRQPRGHOV6XFKLWHPVZLOOQRWEHGLVSOD\HG
Number
01
02
03
04
05
06
07
08
09
10
11
12
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
Data Item
(Operation Mode)
(Set Temperature)
(Return Air Temperature)
(Remote Controller Thermistor Tempeature)
(Indoor Heat Exchanger Thermistor / U Bend)
(Indoor Heat Exchanger Thermistor /Capillary)
(Indoor Heat Exchanger Thermistor /Gas Header)
(Indoor Unit Fan Speed)
(Frequency Requirements)
(Response Frequency)
(Pulse of Indoor Unit Expansion Value)
(Total Running Hours of The Indoor Unit)
(Outdoor Air Temperature)
(Outdoor Heat Exchanger Thermistor)
(Outdoor Heat Exchanger Thermistor)
(Compressor Frequency)
(High Pressure)
(Low Pressure)
(Discharge Pipe Temperature)
(Comp Bottom
Temperature)
(Current)
(Target Super Heat)
(Super Heat)
(Discharge Pipe Super Heat)
(Protection State No. of The Compressor)
(Outdoor Unit Fan Speed)
(63H1 On/Off)
(Defrost Control On/Off)
(Total Running Hours of The Compressor)
(Pulse of The Outdoor Unit Expansion Valve EEVC)
(Pulse of The Outdoor Unit Expansion Valve EEVH)
٨
Details of Compressor protection status No. 33
No.
Contents of display
In case of FDC71-140 refer to
"0"
Normal
"1"
Discharge pipe temperature protection control
P.325
䋬䋨㪍䋩
.(a).1)
"2"
Discharge pipe temperature anomaly
P.325
䋬䋨㪍䋩
.(a).2)
"3"
Current safe control of inverter primary current
P.327
䋬䋨㪍䋩
.(g)
"4"
High pressure protection control
P.325
䋬䋨㪍䋩
.(b).1)
䋬
P.326
䋬䋨㪍䋩
.(c).1)
"5"
High pressure anomaly
P.325
䋬䋨㪍䋩
.(b).2)
"6"
Low pressure protection control
P.326
䋬䋨㪍䋩
.(e).1)
䇭
"7"
Low pressure anomaly
P.326
䋬䋨㪍䋩
.(e).2)
"8"
Anti-frost prevention control
P.327
䋬䋨㪍䋩
.(k)
"9"
Current cut
P.327
䋬䋨㪍䋩
.(g)
"10"
Power transistor protection control
P.327
䋬䋨㪍䋩
.(h)
"11"
Power transistor anomaly (Overheat)
P.327
䋬䋨㪍䋩
.(i)
"12"
Compression ratio control
P.326
䋬䋨㪍䋩
.(f)
"13"
Spare
"14"
Dewing prevention control
P.328
䋬䋨㪍䋩
.(l)
"15"
Current safe control of inverter secondary current
P.327
䋬䋨㪍䋩
.(g)
"16"
Stop by compressor rotor lock
"17"
Stop by compressor startup failure
P.328
䋬䋨㪍䋩
.(p)
Note(1) Operation data display on the remote controller.
䊶
Data is dispalyed until canceling the protection control.
䊶
In case of multiple protections controlled, only the younger No. is displayed.
Note(2) Common item.
㽲
In heating mode.
During protection control by the command signal for reducing compressor
frequency from indoor unit, No. "4" is displayed.
㽳
In cooling and dehumidifying mode.
During protection control by the command signal for reducing compressor
frequency from indoor unit, No. "8" is displayed.
Summary of Contents for FDC Series
Page 95: ... 94 12 PAC T 173 Models FDT100VF 125VF 140VF H H H H H C B A F G D G PJF000Z285 ...
Page 98: ... 97 12 PAC T 173 Models FDEN60VF 71VF C 2 C 1 A B A B D C 1 C 2 C 1 C 2 E G F B PFA003Z817 ...
Page 113: ... 112 12 PAC T 173 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 278: ... 277 12 PAC T 173 ー K ...
Page 346: ... 345 12 PAC T 173 Power PCB 1BSU OVNCFS 4GRNCEG VJG 2 ...
Page 518: ... 517 12 PAC T 173 3 5 SUPER LINK E BOARD SC ADNA E F SL2NA E and SL3N AE BE to control ...
Page 519: ... 518 12 PAC T 173 ...