377
-
'12 • PAC-T-173
WAIT
Communication error at
initial operation (2/3)
(Models SRC40-60)
1. Applicable model
5. Troubleshooting
Models SRC40-60
When the fuse is blown, the
method to inspect inverter
before replacing the power
supply fuse
Diagnosis
Countermeasure
Replace the outdoor
power PCB
YES
YES
NO
YES
Replace the outdoor
control PCB
NO
Replace the
reactor.
NO
Isn’t there
a short-circuit between phases of
outdoor power PCB?
Aren’t there
cracks or burning on the power
ransistor module or diode
stack?
Isn’t reactor the anomalous?
Replace fuse.
2. Error detection method
3. Condition of Error displayed
4. Presumable cause
• Blown fuse
• Faulty outdoor power PCB
• Faulty outdoor control PCB
• Faulty reactor
Note:
Error code
Remote controller:
LED
Green
Red
Indoor
Outdoor
–
2 times flash
Stays OFF
Keeps flashing
Content