381
-
'12 • PAC-T-173
Error code
Remote controller:
LED
Green
Red
Indoor
Outdoor
Content
WAIT
Communication error at
initial operation (3/3)
(Models FDC71-140)
.HHSVÀDVKLQJ
.HHSVÀDVKLQJ
Stays OFF
WLPHVÀDVK
1. Applicable model
5. Troubleshooting
Models FDC71-140
Diagnosis
Countermeasure
NO
YES
NO
YES
YES
NO
YES
NO
Replace the
noise filter.
Method to check for inverter PCB before
replacement of blown power supply fuse.
Replace the
inverter PCB.
Replace the reactor.
Replace the electrolytic
capacitor.
NO
Replace the power
supply fuse.
YES
Isn’t there a
short-circuit between phases of the
noise filter?
Isn’t there a
short-circuit between phases of inverter PCB
input terminals?
Isn’t there
any crack, burning on the power
transistor module?
Is the reactor OK?
Is the
electrolytic capacitor
OK?
From previous page
2. Error detection method
3. Condition of Error displayed
4. Presumable cause
• Blown fuse
• Faulty noise filter
• Faulty inverter PCB
• Faulty reactor
• Faulty electrolytic capacitor
Note:
Summary of Contents for FDC Series
Page 95: ... 94 12 PAC T 173 Models FDT100VF 125VF 140VF H H H H H C B A F G D G PJF000Z285 ...
Page 98: ... 97 12 PAC T 173 Models FDEN60VF 71VF C 2 C 1 A B A B D C 1 C 2 C 1 C 2 E G F B PFA003Z817 ...
Page 113: ... 112 12 PAC T 173 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 278: ... 277 12 PAC T 173 ー K ...
Page 346: ... 345 12 PAC T 173 Power PCB 1BSU OVNCFS 4GRNCEG VJG 2 ...
Page 518: ... 517 12 PAC T 173 3 5 SUPER LINK E BOARD SC ADNA E F SL2NA E and SL3N AE BE to control ...
Page 519: ... 518 12 PAC T 173 ...