385
-
'12 • PAC-T-173
Error code
Remote controller:
LED
Green
Red
Indoor
Outdoor
Content
E6
Indoor heat exchanger
temperature thermistor anomaly
.HHSVÀDVKLQJ WLPHÀDVK
.HHSVÀDVKLQJ
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
NO
NO
YES
Is the
connection of indoor heat
exchanger temperature thermistor
connector OK?
Are
characteristics of indoor
heat exchanger temperature
thermistor OK?
YES
Temperature-resistance characteristic
T
emperature thermistor resistance (k
)
Temperature (°C)
15
10
5
0
10
30
40
20
50
(Broken wire)
(Short circuit)
5k
at 25
°C
Correct.
ª
Insert connector
securely.
Defective indoor heat
exchanger temperature
thermistor
ª
Replace.
Defective indoor control
PCB
ª
Replace.
(Defective indoor unit heat
exchanger temperature
thermistor input circuit)
2. Error detection method
Anomalously low temperature
or high temperature (resistance)
is detected on the indoor heat
exchanger thermistor (ThI-R1,
R2 or R3).
3. Condition of Error displayed
• When the temperature
thermistor detects -40°C
or lower for 5 seconds
continuously, the compressor
stops. After 3-minutes delay,
the compressor starts again
automatically, but if this
error occurs again within
60 minutes after the initial
detection.
• Or if 70°C or higher is
detected for 5 seconds
continuously.
4. Presumable cause
• Defective indoor heat
exchanger thermistor
connector
• Indoor heat exchanger
temperature thermistor
anomaly
• Faulty indoor control PCB
Note:
Summary of Contents for FDC Series
Page 95: ... 94 12 PAC T 173 Models FDT100VF 125VF 140VF H H H H H C B A F G D G PJF000Z285 ...
Page 98: ... 97 12 PAC T 173 Models FDEN60VF 71VF C 2 C 1 A B A B D C 1 C 2 C 1 C 2 E G F B PFA003Z817 ...
Page 113: ... 112 12 PAC T 173 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 278: ... 277 12 PAC T 173 ー K ...
Page 346: ... 345 12 PAC T 173 Power PCB 1BSU OVNCFS 4GRNCEG VJG 2 ...
Page 518: ... 517 12 PAC T 173 3 5 SUPER LINK E BOARD SC ADNA E F SL2NA E and SL3N AE BE to control ...
Page 519: ... 518 12 PAC T 173 ...