'12 • PAC-T-173
Error code
Remote controller:
LED
Green
Red
Indoor
Outdoor
Content
E18
Address setting error of
master and slave indoor units
Keeps flashing 1 times flash
Keeps flashing Stays Off
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Return address No. to
“IU …” using [
▲
] or
[
▲
] button.
2. Error detection method
IU address has been set using
the “Master IU address set”
function of remote controller.
3. Condition of Error displayed
Same as above
4. Presumable cause
Same as above
Note:
Is “Master IU
address set” function of remote
controller used?
E18 occurs
YES