Error code
Remote controller:
LED
Green
Red
Indoor
Outdoor
Content
E19
Indoor unit operation check,
drain motor check setting error
.HHSVÀDVKLQJ WLPHÀDVK
.HHSVÀDVKLQJ
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is SW7-1
on the indoor control
PCB ON ?
E19 occurs
when the power ON
NO
YES
Defective indoor control
PCB (Defective SW7)
ª
Replace
Turn SW7-1 on the indoor
control PCB OFF and reset
the power
2. Error detection method
After indoor operation check,
when the communication
between indoor and outdoor
unit is established and SW7-1 is
still kept ON.
3. Condition of Error displayed
Same as above
4. Presumable cause
Mistake in SW7-1 setting
(Due to forgetting to turn OFF
SW7-1 after indoor operation
check)
Note: