397
-
'12 • PAC-T-173
Error code
Remote controller:
LED
Green
Red
Indoor
Outdoor
Content
E35
Cooling overload operation
(Model SRC40-60 only)
1. Applicable model
5. Troubleshooting
Model SRC40-60
Diagnosis
Countermeasure
Are normal
the characteristics of
outdoor heat exchanger
temperature thermistor
normal?
Is
the temperature
(measured actually) at
direction of error
correct?
NO
YES
YES
Is the
unit operating in
the state of cooling
overload?
Is the high
pressure control
normal
YES
YES
* For the characteristics of outdoor
heat exchanger temperature
thermistor, refer to E37.
NO
NO
NO
Replace outdoor heat
exchanger temperature
thermistor.
Check unit side.
• Isn’t the air circulation
of outdoor unit short-
circuited?
• Are installation spaces
adequate?
• Isn’t there any fouling
or clogging on heater
exchanger?
Control operation check*
Defective outdoor control
PCB
ª
Replace.
Excessive refrigerant
amount: Recharge
refrigerant by weighing
proper amount on a scale.
2. Error detection method
Anomalous stop
Reset
53
63
Outdoor heat exchanger temperature (°C)
3. Condition of Error displayed
When anomalous outdoor heat
exchanger temperature occurs
5 times within 60 minutes
or 63°C or higher continues
for 10 minutes, including the
compressor stop.
4. Presumable cause
• Defective outdoor heat
exchanger temperature
thermistor
• Defective outdoor control
PCB
• Indoor, outdoor unit
installation spaces
• Short-circuit of air on indoor,
outdoor units
• Fouling, clogging of heat
exchanger
• Excessive refrigerant quantity
Note:
2 times flash
Stays OFF
Keeps flashing
–
Summary of Contents for FDC Series
Page 95: ... 94 12 PAC T 173 Models FDT100VF 125VF 140VF H H H H H C B A F G D G PJF000Z285 ...
Page 98: ... 97 12 PAC T 173 Models FDEN60VF 71VF C 2 C 1 A B A B D C 1 C 2 C 1 C 2 E G F B PFA003Z817 ...
Page 113: ... 112 12 PAC T 173 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 278: ... 277 12 PAC T 173 ー K ...
Page 346: ... 345 12 PAC T 173 Power PCB 1BSU OVNCFS 4GRNCEG VJG 2 ...
Page 518: ... 517 12 PAC T 173 3 5 SUPER LINK E BOARD SC ADNA E F SL2NA E and SL3N AE BE to control ...
Page 519: ... 518 12 PAC T 173 ...