408
-
'12 • PAC-T-173
E47
$FWLYH¿OWHUYROWDJHHUURU
(Models SRC40-60)
1. Applicable model
5. Troubleshooting
Models SRC40-60
Diagnosis
Countermeasure
YES
YES
NO
Is the power supply normal?
NO
Check
soldered surfaces on the
outdoor PCB for foreign matter
like dust, fouling,
etc.
YES
Is voltage
within the specified range?
NO
Restore normal condition.
Restore normal condition.
Remove foreign matter like
dust, fouling, etc.
Defective outdoor
PCB
ª
Replace.
2. Error detection method
Error is displayed if the
converter voltage exceeds
DC340V (3 times within 20
minutes). Remote controller
may be set after 3 minutes
delay.
3. Condition of Error displayed
Same as above
4. Presumable cause
• Defective outdoor PCB
• Dust on outdoor PCB
• Anomalous power supply
Note:
Error code
Remote controller:
LED
Green
Red
Content
Indoor
Outdoor
Stays OFF
2 times flash
Keeps flashing
㧙