411
-
'12 • PAC-T-173
E48
1. Applicable model
5. Troubleshooting
Models FDC71-140
Diagnosis
Countermeasure
YES
NO
Does any foreign
material intervene in rotational area
of fan propeller?
NO
Does the
fan rotate smoothly when turned
by hand?
NO
Is DC280V
detected between (CNFAN
(red)-
(blue)) of fan motor
connector?
Is F2 fuse blown?
Is normal state restored?
YES
YES
NO
YES
NO
YES
Power supply reset
(1)
Note (1) Fuse of model 71 is F3.
Remove foreign material.
Replace fan motor.
If resistance between
(Vm):red -
(GND):blue is
detected 1k
:
or lower, it is
faulty.
Check power supply
voltage.
Replace faulty fan motor
and control PCB.
Replace fan motor (If
anomaly persists after
replacing fan motor, replace
control PCB.)
Malfunction by temporary
noise
2. Error detection method
Detected by rotation speed of
outdoor fan motor
3. Condition of Error displayed
When actual rotation speed
of outdoor fan motor (FMo1)
drops to 100min
-1
or lower
for 30 minutes continuously,
the compressor and the
outdoor fan motor stop. After
3-minutes delay, it starts
again automatically, but if this
anomaly occurs 5 times within
60 minutes after the initial
detection.
4. Presumable cause
• Defective outdoor control
PCB
• Foreign material at rotational
area of fan propeller
• Defective fan motor
• Dust on outdoor control PCB
• Blow fuse
• External noise, surge
Note: When E48 error occurs, in almost cases F2 fuse (4A) [Model 71:F3 fuse (2A)]on the outdoor control PCB is blown. There are a lot of cases
that fuse is blown and E48 occurs due to defective fan motor. And even though only the outdoor control PCB ( or fuse) is replaced,, another
trouble (*1) could occur. Therefore when fuse is blown, check whether the fan motor is OK or not.
$IWHUFRQ¿UPLQJWKHIDQPRWRUQRUPDOFKHFNE\SRZHU21'RQWSRZHU21ZLWKRXWFRQ¿UPLQJWKHIDQPRWRUQRUPDO
*1 The error which does not seem to relate E48 may occur like as “
WAIT
”, Stay OFF of LED on outdoor control PCB, inverter
communication error (E45) and etc.
Error code
Remote controller:
LED
Green
Red
Outdoor control PCB
Outdoor inverter
PCB
1 time flash
Keeps flashing
Indoor control PCB
Stays OFF
Keeps flashing
Content
Keeps flashing
Yellow
Outdoor fan motor anomaly
(Models FDC71-140)
Summary of Contents for FDC Series
Page 95: ... 94 12 PAC T 173 Models FDT100VF 125VF 140VF H H H H H C B A F G D G PJF000Z285 ...
Page 98: ... 97 12 PAC T 173 Models FDEN60VF 71VF C 2 C 1 A B A B D C 1 C 2 C 1 C 2 E G F B PFA003Z817 ...
Page 113: ... 112 12 PAC T 173 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 278: ... 277 12 PAC T 173 ー K ...
Page 346: ... 345 12 PAC T 173 Power PCB 1BSU OVNCFS 4GRNCEG VJG 2 ...
Page 518: ... 517 12 PAC T 173 3 5 SUPER LINK E BOARD SC ADNA E F SL2NA E and SL3N AE BE to control ...
Page 519: ... 518 12 PAC T 173 ...