413
-
'12 • PAC-T-173
E49
1. Applicable model
5. Troubleshooting
Models FDC71-140
Diagnosis
Countermeasure
NO
YES
NO
YES
Is the
service valve fully
opened?
Are the
connections of low
pressure sensor and suction pipe
temprerature thermister
connector OK?
NO
YES
NO
YES
Are the
characteristics of
low pressure sensor, suction
pipe temperature
thermistor OK?
Is the low
pressure normal during
operation?
From previous page
Open fully.
Correct.
Defective low pressure
sensor, suction pipe
temperature thermistor
ª
Replace.
Charge refrigerant.
Defective outdoor control
PCB
ª
Replace.
(Defective low pressure
sensor, suction pipe
temperature thermistor
circuits)
2. Error detection method
3. Condition of Error displayed
4. Presumable cause
Note:
Error code
Remote controller:
LED
Green
Red
Outdoor control PCB
Outdoor inverter
PCB
1 time flash
Keeps flashing
Indoor control PCB
Stays OFF
Keeps flashing
Content
Keeps flashing
Yellow
Low pressure error or
low pressure sensor anomaly (2/2)
(Models FDC71-140)
Summary of Contents for FDC Series
Page 95: ... 94 12 PAC T 173 Models FDT100VF 125VF 140VF H H H H H C B A F G D G PJF000Z285 ...
Page 98: ... 97 12 PAC T 173 Models FDEN60VF 71VF C 2 C 1 A B A B D C 1 C 2 C 1 C 2 E G F B PFA003Z817 ...
Page 113: ... 112 12 PAC T 173 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 278: ... 277 12 PAC T 173 ー K ...
Page 346: ... 345 12 PAC T 173 Power PCB 1BSU OVNCFS 4GRNCEG VJG 2 ...
Page 518: ... 517 12 PAC T 173 3 5 SUPER LINK E BOARD SC ADNA E F SL2NA E and SL3N AE BE to control ...
Page 519: ... 518 12 PAC T 173 ...