420
-
'12 • PAC-T-173
E58
Current safe stop
(Models SRC40-60)
1. Applicable model
5. Troubleshooting
Models SRC40-60
When the current safe control
has operated at the compressor
speed of 30 rps or under:
Same as above
• Excessive refrigerant amount
• Indoor,outdoor unit installation
spaces
• Faulty compressor
• Defective outdor air temp.
sensor
• Defective outdoor PCB
Diagnosis
Countermeasure
2. Error detection method
3.Condition of Error displayed
4. Presumable cause
Note:
Is outdoor
ventilation condition
good ?
Inspect
outdor air temp.
sensor
Is the refrigerant
amount nomal ?
Adjust the refrigerant
amount properly.
Secure space for inlet and
outlet.
Replace compressor.
Replace sensor.
Defective outdoor
PCB
¡
Replace.
(Defective outdor air temp.
sensor input circuit)
Inspect
compressor
YES
YES
YES
NO
NO
NO
NO
YES
Error code
Remote controller:
LED
Green
Red
Content
Indoor
Outdoor
Stays OFF
3 times flash
Keeps flashing
㧙
Summary of Contents for FDC Series
Page 95: ... 94 12 PAC T 173 Models FDT100VF 125VF 140VF H H H H H C B A F G D G PJF000Z285 ...
Page 98: ... 97 12 PAC T 173 Models FDEN60VF 71VF C 2 C 1 A B A B D C 1 C 2 C 1 C 2 E G F B PFA003Z817 ...
Page 113: ... 112 12 PAC T 173 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 278: ... 277 12 PAC T 173 ー K ...
Page 346: ... 345 12 PAC T 173 Power PCB 1BSU OVNCFS 4GRNCEG VJG 2 ...
Page 518: ... 517 12 PAC T 173 3 5 SUPER LINK E BOARD SC ADNA E F SL2NA E and SL3N AE BE to control ...
Page 519: ... 518 12 PAC T 173 ...