Error code
Remote controller:
Content
1 time flash
Keeps flashing
6 times flash
–
–
Indoor display
RUN light
TIMER light
Green LED
Yellow LED
Red LED
Outdoor
control PCB
Outdoor
inverter PCB
E41
Power transistor overheat
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
NO
Is DC15V detected
between
②
and
③
on
CNI3?
⑴ ⑵
NO
YES
Is DC15V
detected after disconnecting
outdoor fan motor?
⑴
YES
Note(1) Under anomalous conditions,
ޓޓ
the voltage becomes less than DC14V.
Note(2) How to check the voltage between
②
and
③
of CNI3?
ޓޓޓ
⇒
See E51
E41
⇒
Replace inverter PCB
• Single phase models
• 3-phase models
Replace inverter PCB
Replace outdoor fan motor
Replace outdoor control PCB
If not solved, replace
inverter PCB as well
2. Error detection method
When less than DC14V of
the output voltage is detected
between
②
and
③
on CNI3,
E41
is displayed. (See "Note"
mentioned below)
3. Condition of Error displayed
Same as above.
4. Presumable cause
• Defective inverter PCB
• Defective outdoor fan motor
• Defective outdoor control
PCB
• Delective noise filter PCB
Note:
The "Single phase models" of inverter PAC have no function to output the signal for the power transistor overheat. However
since the power source for the power transistor and the outdoor fan motor is in the same line, when the anomaly of the
outdoor fan motor occurs, E41 is displayed.
-
455
-
'12 • PAC-T-173
Summary of Contents for FDC Series
Page 95: ... 94 12 PAC T 173 Models FDT100VF 125VF 140VF H H H H H C B A F G D G PJF000Z285 ...
Page 98: ... 97 12 PAC T 173 Models FDEN60VF 71VF C 2 C 1 A B A B D C 1 C 2 C 1 C 2 E G F B PFA003Z817 ...
Page 113: ... 112 12 PAC T 173 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 278: ... 277 12 PAC T 173 ー K ...
Page 346: ... 345 12 PAC T 173 Power PCB 1BSU OVNCFS 4GRNCEG VJG 2 ...
Page 518: ... 517 12 PAC T 173 3 5 SUPER LINK E BOARD SC ADNA E F SL2NA E and SL3N AE BE to control ...
Page 519: ... 518 12 PAC T 173 ...