470
-
'12 • PAC-T-173
Model
Item
FDT40VF
Panel
T-PSA-3BW-E
Power source
220-240V~50Hz / 220V~60Hz
Operation data
Cooling
Heating
Nominal capacity
kW
4.0
4.5
Sound Pressure Level
dB(A)
P-Hi : 39 Hi : 33 Me : 31 Lo : 30
Exterior dimensions
Height × Width × Depth
mm
Unit 246 × 840 × 840
Panel 35 × 950 × 950
Exterior appearance
(Munsell color)
Plaster White
(6.8Y8.9/0.2) near equivalent
Net weight
kg
UNIT 22 PANEL 5.5
Heat exchanger
Louver fin & inner grooved tubing
Air handling equipment
Fan type & Q'ty
Turbo fan ×1
Motor <Starting method>
W
50 < Direct line start >
Air flow (Standard)
CMM
P-Hi : 20 Hi : 18 Me : 16 Lo : 14
External static pressure
Pa
0
Outdoor air intake
Possible
Air filter, Q'ty
Pocket plastic net ×1 (Washable)
Shock & vibration absorber
Rubber sleeve (for fan motor)
Insulation (noise & heat)
Polyurethane form
Remote controller
wired : RC-EX1A, RC-E5 (option) wireless : RCN-T-36W-E (option)
Room temperature control
Thermostat by electronics
Safety equipment
Overload protection for fan motor
Frost protection thermostat
Installation data
Refrigerant piping size
mm
Liquid line :
φ
6.35 (1/4")
Gas line :
φ
12.7 (1/2")
Connecting method
Flare piping
Drain pump
Built-in Drain pump
Drain
Hose Connectable with VP25
Insulation for piping
Necessary (both Liquid & Gas lines)
IP code
IPXO
Standard Accessories
Mounting kit, Drain hose
Adapted to
RoHS
directive
Item
Indoor air temperature
Outdoor air temperature
Operation
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
Heating
20˚C
7˚C
6˚C
Notes (1) The data are measured at the following conditions.
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber. During operation
these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) If wireless remote controller is used, only 3-speed fan setting (Hi-Me-Lo) is available.
PJF000Z296
2.2 SPECIFICATIONS
(1) Indoor units
(a) Ceiling cassette-4way type (FDT)
Summary of Contents for FDC Series
Page 95: ... 94 12 PAC T 173 Models FDT100VF 125VF 140VF H H H H H C B A F G D G PJF000Z285 ...
Page 98: ... 97 12 PAC T 173 Models FDEN60VF 71VF C 2 C 1 A B A B D C 1 C 2 C 1 C 2 E G F B PFA003Z817 ...
Page 113: ... 112 12 PAC T 173 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 278: ... 277 12 PAC T 173 ー K ...
Page 346: ... 345 12 PAC T 173 Power PCB 1BSU OVNCFS 4GRNCEG VJG 2 ...
Page 518: ... 517 12 PAC T 173 3 5 SUPER LINK E BOARD SC ADNA E F SL2NA E and SL3N AE BE to control ...
Page 519: ... 518 12 PAC T 173 ...