(c) Calculation of total operation characteristics
Since the operation characteristics of V Multi system depend on combination of indoor unit, calculate the total operation characteristics
of the system by using the formulas below according to speciations of each indoor unit or outdoor unit.
1) 1 Phase models
a) Total power consumption
Total power consumption (kW) = Power consumption of outdoor unit +
¤
(Power consumption of indoor unit)
b) Total running current
Total running current (A) = Running current of outdoor unit +
¤
(Running current of indoor unit)
c) Total power factor
Total power factor (%) = [Total power consumption (W) / Total running current (A)
s
Power source]
s
100
Total operation characteristics = Operation characteristic value of outdoor unit + Operation characteristic value of indoor unit
[Example]
(Conditions) Operation Voltage ········ Indoor unit: 220 V, 50 Hz
Outdoor unit: 220 V, 50 Hz
Operation mode ··········· Cooling and Heating
Unit······························· Outdoor unit: FDC140VNX × 1 unit
Indoor unit: FDT71VF × 2 units
Item
Model
FDC140VNX
FDT71VF
Operation characteristics of each unit
(Cooling/Heating)
Power consumption (kW)
Running current (A)
0.08/0.08
0.40/0.40
4.02/4.03
17.6/17.6
Ԙ
Total power consumption (kW)
(Cooling) 4.02 + (0.08 × 2) = 4.18
(Heating) 4.03 + (0.08 × 2) = 4.19
ԙ
Total running current (A)
(Cooling) 17.6 + (0.40 × 2) = 18.4
(Heating) 17.6 + (0.40 × 2) = 18.4
Ԛ
Total power factor (%)
(Cooling) × 100 = 99 %
(Heating) × 100 = 99 %
4.18 × 1000
18.4 × 220
4.19 × 1000
18.4 × 220
.
.
.
.
2) 3 Phase models
a) Total power consumption
Total power consumption (kW) = Power consumption of outdoor unit +
¤
(Power consumption of indoor unit)
b) Total running current
Total running current (A) = Running current of outdoor unit + [
¤
(Running current of indoor unit) × 1/3]
c) Total power factor
Total power factor (%) = [Total power consumption (W) /
㺕㩷
× Total running current (A) × Power source] × 100
Total operation characteristics = Operation characteristic value of outdoor unit + Operation characteristic value of indoor unit
㪊
Summary of Contents for FDC Series
Page 95: ... 94 12 PAC T 173 Models FDT100VF 125VF 140VF H H H H H C B A F G D G PJF000Z285 ...
Page 98: ... 97 12 PAC T 173 Models FDEN60VF 71VF C 2 C 1 A B A B D C 1 C 2 C 1 C 2 E G F B PFA003Z817 ...
Page 113: ... 112 12 PAC T 173 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 278: ... 277 12 PAC T 173 ー K ...
Page 346: ... 345 12 PAC T 173 Power PCB 1BSU OVNCFS 4GRNCEG VJG 2 ...
Page 518: ... 517 12 PAC T 173 3 5 SUPER LINK E BOARD SC ADNA E F SL2NA E and SL3N AE BE to control ...
Page 519: ... 518 12 PAC T 173 ...