499
-
'12 • PAC-T-173
Installation of the controller holder
Caution
DO NOT install it on the following places
1) Places exposed to direct sunlight
2) Places near heat devices
3) High humidity places
4) Hot surface or cold surface enough to generate
condensation
5) Places exposed to oil mist or steam directly
6) Uneven surface
Installation tips for the remote controller holder
• Adjust and keep the holder upright.
• Tighten the screw to the end to avoid scratching
the remote controller.
• DO NOT attach the holder to plaster wall.
Ԙ
Detach the back lid.
ԙ
Insert the batteries. (two AAA batteries)
Ԛ
Reattach the back lid.
٨
After safety con rmation, turn on the power.
٨
Transmit a cooling operation command with wireless remote controller, while the backup
button on the receiver is pressed.
٨
If the backup button on the receiver is pressed during a test run, it will end the test run.
٨
If you cannot operate the unit properly during a test run, please check by consulting with
inspection guides on the wiring diagram of outdoor units.
Wood screw
Holder for
remote
controller
This setting is to avoid the mixed communication with other household electric
appliances or the mixed communication when two receivers are located closely.
Ԙ
Setting change of the wireless remote controller
Pressing ACL and AIRFLOW button at the same time or inserting the batteries
with pressing AIRFLOW button will customize the signal.
Note
*When the batteries are removed, the setting will return to the default setting.
Make sure to reset it when the batteries are replaced.
ԙ
Setting the PCB of the receiver
Turn SW1-1 off.
Do both procedures
Ԙ
and
ԙ
.
٨
Wireless remote controller
Setting to
avoid mixed
communication.
٨
PCB of the receiver
SW1-4
(Auto restart)
SW1-1
(Customized signal
setting to avoid
mixed communication)
SW1-2
(Receiver master/slave
setting)
SW1-1
Customized signal setting to
avoid mixed communication
ON
: N o r m a l
OFF : R e m o t e
SW1-2
Receiver master/slave setting
ON
: M a s t e r
OFF : S l ave
SW1-4
Auto restart
ON
: Va l i d
OFF : I nva l i d
: Default setting
Up to 16 indoor units can be connected.
Ԙ
Connect the XY terminal with 2-core wire.
As for the size, refer to the following note.
ԙ
For Packaged air conditioner series, set the
indoor unit address with SW2 on the indoor
unit PCB from [0] to [F] so as not to duplicate.
Ԛ
For VRF series, set the indoor unit address with SW1, SW2 and SW5-2 on the
indoor unit PCB from [000] to [127] so as not to duplicate.
KIT
Restrictions on the thickness and length of wire
(Maximun total extension 600m.)
Within 100m x 0.3 mm
2
Within 200m x 0.5 mm
2
Within 300m x 0.75mm
2
Within 400m x 1.25mm
2
Within 600m x 2.0 mm
2
Standard
Terminal block
Remote controller
Indoor unit (1)
Address (0)
Indoor unit (2)
Address (1)
Indoor unit (16)
Address (F)
Up to two receivers can be installed in one indoor unit group.
Switch
Setting
Function
SW1-2
ON
Master
OFF
Slave
Indoor unit
RCN-KIT
SW1[Master]
RCN-KIT
SW1[Slave]
Remote controller line
(Non-polarized)
ԛ
Remotecontroller
How to insert batteries
Ԝ
Cooling test run operation
(A) Methods of avoiding the malfunction due to the mixed communication
(B) Control plural indoor units with one remote controller
(C) Master/Slave setting when using plural remote controller
ԝ
Setting of wireless remote controller and receiver
CHECK MODE
ON/
OFF
CHECK
FILTER
CHECK
TIMER
RUN/
CHECK
Back-up button
(D) Change setting of auto mode operation
Auto mode operation is prohibited to be selected for KX models (except for KXR
models).
Therefore be sure to change setting of remote controller to disable the auto mode
operation for these models according to the following procedure.
While pressing the MODE button, press the ACL switch, or while pressing the
MODE button, insert the batteries to the remote controller. Then the auto mode
can be invalid.
Attention
When the batteries are removed, it is returned to initial setting (Auto mode
becomes valid).
Accordingly when replacing the batteries, be sure to perform the above operation
once again.
(E) Change setting of fan speed
While pressing the FAN SPEED button, press the ACL switch, or while pressing
the FAN SPEED button, insert the batteries to the remote controller. Then the
fan speed can be changed from 2-speed setting to 3-speed setting.
When changing fan speed setting of remote controller, be sure to perform the same
fan speed setting as that of the indoor unit model to be used.
Attention
When the batteries are removed, it is returned to initial setting (Fan speed setting
is 2-speed).
Accordingly when replacing the batteries, be sure to perform the above operation
once again.
Summary of Contents for FDC Series
Page 95: ... 94 12 PAC T 173 Models FDT100VF 125VF 140VF H H H H H C B A F G D G PJF000Z285 ...
Page 98: ... 97 12 PAC T 173 Models FDEN60VF 71VF C 2 C 1 A B A B D C 1 C 2 C 1 C 2 E G F B PFA003Z817 ...
Page 113: ... 112 12 PAC T 173 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 278: ... 277 12 PAC T 173 ー K ...
Page 346: ... 345 12 PAC T 173 Power PCB 1BSU OVNCFS 4GRNCEG VJG 2 ...
Page 518: ... 517 12 PAC T 173 3 5 SUPER LINK E BOARD SC ADNA E F SL2NA E and SL3N AE BE to control ...
Page 519: ... 518 12 PAC T 173 ...