516
-
'12 • PAC-T-173
Ɣ
Cable connection for SRK twin / triple installation
Connect the same pairs number of terminal block " , ,and
"and "
and
" between master
and slave indoor units.
Do the same address setting of all inside units belong to same refrigerant system by rotary switch
SW1 on SC-BIKN-E’s PCB (Printed circuit board).
Set slave indoor unit as "slave 1" through "slave 3" by address switch SW3-1, 3-2 on SC-BIKN-E’s
PCB.
When the
button on the remote control unit is pressed after turning on the power, an
indoor unit's address number will be displayed. Do not fail to confirm that the connected indoor unit's
numbers are displayed on the remote control unit by pressing the
or
button.
Method of setting Master/Slave of SC-BIKN-E
(Factory setting: “Master”)
PCB
SW
SW3-1
OFF
OFF
OFF
ON
ON
ON
ON
OFF
SW3-2
SC-BIKN-E
Master
Slave 1
Slave 2
Slave 3
AIR CON NO.
Remote controller
Outdoor Unit
Power source
Earth leakage
breaker
Circuit breaker
Earth
Earth
Earth
Earth
Earth
Remote controller line (no polarity)
Indoor Unit Master
Indoor Unit Slave 1
Indoor Unit Slave 2
Indoor Unit Slave 3
SC-BIKN-E Master
SC-BIKN-E's PCB
Connection Cable
SC-BIKN-E Slave 1
SC-BIKN-E Slave 2
SC-BIKN-E Slave 3
Twin type
Triple type
Double twin type
DIP switch
(SW3-2)
DIP switch
(SW3-1)
Rotary switch
(SW1)
RKZ012A092
Summary of Contents for FDC Series
Page 95: ... 94 12 PAC T 173 Models FDT100VF 125VF 140VF H H H H H C B A F G D G PJF000Z285 ...
Page 98: ... 97 12 PAC T 173 Models FDEN60VF 71VF C 2 C 1 A B A B D C 1 C 2 C 1 C 2 E G F B PFA003Z817 ...
Page 113: ... 112 12 PAC T 173 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 278: ... 277 12 PAC T 173 ー K ...
Page 346: ... 345 12 PAC T 173 Power PCB 1BSU OVNCFS 4GRNCEG VJG 2 ...
Page 518: ... 517 12 PAC T 173 3 5 SUPER LINK E BOARD SC ADNA E F SL2NA E and SL3N AE BE to control ...
Page 519: ... 518 12 PAC T 173 ...