-
59
-
'12 • PAC-T-173
Model
Item
FDU140VNXVD
Indoor unit
FDU140VD
Outdoor unit
FDC140VNX
—
Power source
220-240V~50Hz
Operation data
Cooling
Heating
Nominal capacity
kW
14.0 [ 5.0 (Min.)~16.0 (Max.)]
16.0 [ 4.0 (Min.)~18.0 (Max.)]
Power consumption
kW
4.20
4.30
Running current
A
18.6
19.1
Power factor
%
98
98
Inrush current
A
5 < Max.running current 30 >
Sound Pressure Level
dB(A)
Hi : 43 Lo : 38
Cooling : 49 Heating : 52
Exterior dimensions
Height × Width × Depth
mm
350 × 1,370 × 650
1,300 × 970 × 370
Exterior appearance
(Munsell color)
—
Stucco White
(4.2Y7.5/1.1) near equivalent
Net weight
kg
63
105
Refrigerant equipment
Compressor type & Q'ty
—
RMT5134MDE2 × 1
Starting method
—
Direct line start
Refrigerant oil
—
0.9 (M-MA68)
Heat exchanger
Louver fin & inner grooved tubing
M shape fin & inner grooved tubing
Refrigerant control
—
Electronic expansion valve
Air handling equipment
Fan type & Q'ty
Centrifugal fan × 2
Propeller fan × 2
Motor <Starting method>
W
370 < Direct line start >
86 × 2 < Direct line start >
Air flow (Standard)
CMM
Hi : 42 Lo : 33.5
100
External static pressure
Pa
Standard : 60 Max : 130
0
Outdoor air intake
Possible (on return duct)
—
Air filter, Q'ty
Procure locally
—
Shock & vibration absorber
Rubber sleeve (for fan motor)
Rubber sleeve (for Compressor)
Insulation (noise & heat)
Polyurethane form
—
Electric heater
W
—
20 (Crank case heater)
Remote controller
wired : RC-E5 (option) wireless : RCN-KIT3-E (option)
Room temperature control
Thermostat by electronics
—
Safety equipment
Internal thermostat for fan motor
Frost protection thermostat
Internal thermostat for fan motor
Abnormal discharge temperature protection.
Installation data
Refrigerant piping size
mm
Liquid line : I/U
φ
9.52 (3/8") Pipe
φ
9.52 (3/8") × 0.8 O/U
φ
9.52 (3/8")
Gas line
: I/U
φ
15.88 (5/8") Pipe
φ
15.88 (5/8") × 1.0 O/U
φ
15.88 (5/8")
Connecting method
Flare piping
Flare piping
Refrigerant line (one way) length
Max.100m
Vertical height difference between
outdoor unit and indoor unit
Max.30m (Outdoor unit is higher)
See page 152
Max.15m (Outdoor unit is lower)
Refrigerant Quantity
R410A 4.5kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain pump
Built-in Drain pump
—
Drain
Hose Connectable with VP20
Holes size
φ
20 × 3pcs
Insulation for piping
Necessary (both Liquid & Gas lines)
IP code
IPXO
IP24
Standard Accessories
Drain hose
Edging
Adapted to
RoHS
directive
Item
Indoor air temperature
Outdoor air temperature
External static pressure
of indoor unit [Pa]
Operation
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
60
Heating
20˚C
7˚C
6˚C
Notes (1) The data are measured at the following conditions.
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber. During operation these value are somewhat higher due to
ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz
(5) External static pressure can be changed from standard external static pressure (factory setting) to maximum external static
pressuer (high static pressure setting) by remote controller.
(6) Value of sound pressure level become increased 5dB(A), when external static pressure is 130Pa.
PJD001Z311
Summary of Contents for FDC Series
Page 95: ... 94 12 PAC T 173 Models FDT100VF 125VF 140VF H H H H H C B A F G D G PJF000Z285 ...
Page 98: ... 97 12 PAC T 173 Models FDEN60VF 71VF C 2 C 1 A B A B D C 1 C 2 C 1 C 2 E G F B PFA003Z817 ...
Page 113: ... 112 12 PAC T 173 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 278: ... 277 12 PAC T 173 ー K ...
Page 346: ... 345 12 PAC T 173 Power PCB 1BSU OVNCFS 4GRNCEG VJG 2 ...
Page 518: ... 517 12 PAC T 173 3 5 SUPER LINK E BOARD SC ADNA E F SL2NA E and SL3N AE BE to control ...
Page 519: ... 518 12 PAC T 173 ...