'12 • PAC-T-173
Model
Item
FDT40ZJXVF
Indoor unit
FDT40VF
Outdoor unit
SRC40ZJX-S
Panel
T-PSA-3BW-E
Power source
220-240V~50Hz / 220V~60Hz
Operation data
Cooling
Heating
Nominal capacity
kW
4.0 [ 1.1 (Min.)~4.7 (Max.)]
4.5 [ 0.6 (Min.)~5.4 (Max.)]
Power consumption
kW
0.930
1.06
Running current
A
4.4 / 4.6
5.1 / 5.3
Power factor
%
92 / 92
90 / 91
Inrush current
A
5 < Max.running current 12 >
Sound Pressure Level
dB(A)
P-Hi : 39 Hi : 33 Me : 31 Lo : 30
50
Exterior dimensions
Height × Width × Depth
mm
Unit 246 × 840 × 840
Panel 35 × 950 × 950
640 × 800 (+71) × 290
Exterior appearance
(Munsell color)
Plaster White
(6.8Y8.9/0.2) near equivalent
Stucco White
(4.2Y7.5/1.1) near equivalent
Net weight
kg
UNIT 22 PANEL 5.5
45
Refrigerant equipment
Compressor type & Q'ty
—
RMT5113MCE2 (Twin Rotary type) × 1
Starting method
—
Direct line start
Refrigerant oil
—
0.45 MA68
Heat exchanger
Louver fin & inner grooved tubing
M shape fin & inner grooved tubing
Refrigerant control
—
Capillary tubes + Electronic expansion valve
Air handling equipment
Fan type & Q'ty
Turbo fan × 1
Propeller fan × 1
Motor <Starting method>
W
50 < Direct line start >
34 < Direct line start >
Air flow (Standard)
CMM
P-Hi : 20 Hi : 18 Me : 16 Lo : 14
Cooling : 36 Heating : 33
Available static pressure
Pa
0
0
Outside air intake
Possible
—
Air filter, Q'ty
Pocket plastic net × 1 (Washable)
—
Shock & vibration absorber
Rubber sleeve (for fan motor)
Rubber sleeve (for Compressor)
Insulation (noise & heat)
Polyurethane form
—
Electric heater
W
—
—
Remote controller
wired : RC-EX1A, RC-E5 (option) wireless : RCN-T-36W-E (option)
Room temperature control
Thermostat by electronics
—
Safety equipment
Overload protection for fan motor
Frost protection thermostat
Internal thermostat for fan motor
Abnormal discharge temperature protection.
Installation data
Refrigerant piping size
mm
Liquid line : I/U
φ
6.35 (1/4") Pipe
φ
6.35 (1/4") × 0.8 O/U
φ
6.35 (1/4")
Gas line
:
φ
12.7 (1/2")
φ
12.7 (1/2") × 0.8
φ
12.7 (1/2")
Connecting method
Flare piping
Flare piping
Refrigerant line (one way) length
Max.30m
Vertical height difference between
outdoor unit and indoor unit
Max.20m (Outdoor unit is higher)
See page 152
Max.20m (Outdoor unit is lower)
Refrigerant Quantity
R410A 1.5kg in outdoor unit (incl. the amount for the piping of : 15m)
Drain pump
Built-in Drain pump
—
Drain
Hose Connectable with VP25
Holes size
φ
20 × 5pcs
Insulation for piping
Necessary (both Liquid & Gas lines)
IP code
IPXO
IPX4
Standard Accessories
Mounting kit, Drain hose
Drain elbow, Drain hole grommet
1.1 SPECIFICATIONS
(1) Ceiling cassette-4way type (FDT)
(a) Single type
Adapted to
RoHS
directive
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber. During operation these value are somewhat higher due to
ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) When wireless remote controller is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJF000Z296
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
Operation
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
Heating
20˚C
7˚C
6˚C
Summary of Contents for FDC Series
Page 95: ... 94 12 PAC T 173 Models FDT100VF 125VF 140VF H H H H H C B A F G D G PJF000Z285 ...
Page 98: ... 97 12 PAC T 173 Models FDEN60VF 71VF C 2 C 1 A B A B D C 1 C 2 C 1 C 2 E G F B PFA003Z817 ...
Page 113: ... 112 12 PAC T 173 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 278: ... 277 12 PAC T 173 ー K ...
Page 346: ... 345 12 PAC T 173 Power PCB 1BSU OVNCFS 4GRNCEG VJG 2 ...
Page 518: ... 517 12 PAC T 173 3 5 SUPER LINK E BOARD SC ADNA E F SL2NA E and SL3N AE BE to control ...
Page 519: ... 518 12 PAC T 173 ...