-
81
-
'12 • PAC-T-173
FDF125VNXVD
Indoor unit
FDF125VD
Outdoor unit
FDC125VNX
Power source
220-240V~50Hz / 220V~60Hz
Operation data
Cooling
Heating
Nominal capacity
kW
12.5 [ 5.0 (Min.)~14.0 (Max.)]
14.0 [ 4.0 (Min.)~17.0 (Max.)]
Power consumption
kW
3.89
3.88
Running current
A
17.3 / 18.0
17.2 / 18.0
Power factor
㧑
98
98
Inrush current
A
5 < Max.running current 26 >
Sound Pressure Level
dB(A)
P-Hi : 54 Hi : 50 Me : 48 Lo : 44
Cooling : 48
ẅ
Heating : 50
Exterior dimensions
Height × Width × Depth
Exterior appearance
Ceramic White
Stucco White
(Munsell color )
(N8.0) near equivalent
(4.2Y7.5/1.1) near equivalent
Net weight
kg
52
105
Refrigerant equipment
Compressor type & Q'ty
—
RMT5134MDE2 × 1
Starting method
—
Direct line start
Refrigerant oil
—
0.9 M-MA68
Heat exchanger
Louver fine & inner grooved tubing
M shape fin & inner grooved tubing
Refrigerant control
—
Electronic expansion valve
Air handling equipment
Fan type & Q'ty
Centrifugal fan × 1
Propeller fan × 2
Motor <Starting method>
W
157 < Direct line start >
86 × 2 < Direct line start >
Air flow (Standard)
CMM
P-Hi
ᾉ
29 Hi
ᾉ
26 Me
ᾉ
23 Lo
ᾉ
19
100
External static pressure
Pa
0
Outside air intake
Not possible
—
Air filter, Q'ty
Plastic net × 1 (Washable)
—
Shock & vibration absorber
Rubber sleeve (for fan motor)
Rubber sleeve (for Compressor )
Insulation (noise & heat)
Polyurethane form
—
Electric heater
W
—
20 (Crank case heater)
Remote controller
RC-E5 Installed / wireless : RCN-KIT3-E
ᴾ
(option)
Room temperature control
Thermostat by electronics
—
Safety equipment
Overload protection for fan motor
Internal thermostat for fan motor
Frost protection thermostat
Abnormal discharge temperature protection.
Installation data
Refrigerant piping size
Connecting method
Flare piping
Flare piping
Refrigerant line (one way) length
Vertical height difference between
outdoor unit and indoor unit
Refrigerant
ᴾ
Quantity
R410A 4.5kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain pump
—
—
Drain
Insulation for piping
Necessary (both Liquid & Gas lines)
Model
Item
mm
1,850
ᴾ
× 600
ᴾ
× 320
1,300
ᴾ
× 970
ᴾ
× 370
mm
Max.30m (Outdoor unit is higher)
Max.15m (Outdoor unit is lower)
Hose Connectable with VP20
See page 152
Max.100m
Gas line
:
₥
15.88 (5/8")
₥
15.88 (5/8") × 1.0
₥
15.88 (5/8")
Liquid line : I/U
₥
9.52 (3/8") Pipe
₥
9.52 (3/8") × 0.8 O/U 9.52 (3/8")
Holes size
᷑
20 × 3pcs
Adapted to
RoHS
directive
Standard Accessories
Mounting kit
Edging
Notes (1) The data are measured at the following conditions.
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber. During operation
ẅ
these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) If wireless remote controller is used, only 3-speed fan setting (Hi-Me-Lo) is available.
Indoor air temperature
Operation
DB
27
o
C
20
o
C
7
o
C
6
o
C
19
o
C
35
o
C
24
o
C
WB
DB
WB
Cooling
Heating
Item
Outdoor air temperature
0
IP code
IPXO
IP24
PGA000Z780
Summary of Contents for FDC Series
Page 95: ... 94 12 PAC T 173 Models FDT100VF 125VF 140VF H H H H H C B A F G D G PJF000Z285 ...
Page 98: ... 97 12 PAC T 173 Models FDEN60VF 71VF C 2 C 1 A B A B D C 1 C 2 C 1 C 2 E G F B PFA003Z817 ...
Page 113: ... 112 12 PAC T 173 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 278: ... 277 12 PAC T 173 ー K ...
Page 346: ... 345 12 PAC T 173 Power PCB 1BSU OVNCFS 4GRNCEG VJG 2 ...
Page 518: ... 517 12 PAC T 173 3 5 SUPER LINK E BOARD SC ADNA E F SL2NA E and SL3N AE BE to control ...
Page 519: ... 518 12 PAC T 173 ...