87
-
'12 • PAC-T-173
Nominal capacity
kW
10.0 [ 4.0 (Min.)~11.2 (Max.)]
11.2 [ 4.0 (Min.)~12.5 (Max.)]
Power consumption
kW
2.66
2.60
Running current
A
11.8 / 12.3
11.5 / 12.1
Power factor
㧑
98
98
Inrush current
A
5 < Max.running current 24 >
Sound Pressure Level
dB(A)
Hi : 47 Me : 40 Lo : 27(C) / Hi : 48 Me : 40 Lo : 33(H)
Cooling : 48
ẅ
Heating : 50
Exterior dimensions
Height × Width × Depth
Exterior appearance
Fine snow
Stucco White
(Munsell color)
(8.0Y 9.3/0.1) near equivalent
(4.2Y7.5/1.1) near equivalent
Net weight
kg
15
105
Refrigerant equipment
Compressor type & Q'ty
—
RMT5134MDE2 × 1
Starting method
—
Direct line start
Refrigerant oil
—
0.9 M-MA68
Heat exchanger
Louver fine & inner grooved tubing
M shape fin & inner grooved tubing
Refrigerant control
—
—
Electronic expansion valve
Air handling equipment
Fan type & Q'ty
Tangential fan × 1
Propeller fan × 2
Motor <Starting method>
W
27 < Direct line start >
86 × 2 < Direct line start >
Air flow (Standard)
CMM
Hi : 13.5 Me : 11 Lo : 8(C) / Hi : 16.5 Me : 14.5 Lo : 10.5(H)
100
External static pressure
Pa
0
Outside air intake
Not possible
—
0
Air filter, Q'ty
Polypropylene net (washable) × 2
—
Shock & vibration absorber
Rubber sleeve (for Compressor )
Insulation (noise & heat)
Polyurethane form
—
Electric heater
W
—
20 (Crank case heater)
Remote controller
RC-E5 (option) & SC-BIKN-E (Interface kit, option)
Room temperature control
Thermostat by electronics
—
Safety equipment
Internal thermostat for fan motor
Internal thermostat for fan motor
Frost protection thermostat
Abnormal discharge temperature protection.
Installation data
Refrigerant piping size
Connecting method
Flare piping
Flare piping
Refrigerant line (one way) length
Vertical height difference between
outdoor unit and indoor unit
Refrigerant
ᴾ
Quantity
R410A 4.5kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain pump
—
—
Drain
Insulation for piping
Necessary (both Liquid & Gas lines)
IP code
IPXO
IP24
Standard Accessories
Mounting kit, Drain hose
Edging
Notes (1) The data are measured at the following conditions.
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber. During operation
ẅ
these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.
mm
309 × 890 × 220
1,300 × 970 × 370
mm
SRK100VNXPZJX
Indoor unit
SRK50ZJX-S1 (2 units)
Outdoor unit
FDC100VNX
Power source
220-240V~50Hz / 220V~60Hz
Operation data
Cooling
Heating
Item
Max.100m
Max.30m (Outdoor unit is higher)
Max.15m (Outdoor unit is lower)
Hose Connectable with VP16
Holes size
᷑
20 × 3pcs
See page 152
Indoor air temperature
Operation
DB
27
o
C
20
o
C
7
o
C
6
o
C
19
o
C
35
o
C
24
o
C
WB
DB
WB
Cooling
Heating
Item
Outdoor air temperature
Model
Liquid line : I/U
₥
6.35 (1/4")
ℳ
₥
9.52 (3/8") × 0.8
Ⅎ⅙
9.52 (3/8") × 0.8
‒‒‒
O/U
⅙
9.52 (3/8")
Gas line
: I/U
⅙
12.7 (1/2")
ℳ⅙
12.7 (1/2") × 0.8
Ⅎ⅙
15.88 (5/8") × 1.0
‒‒
O/U
⅙
15.88 (5/8")
(6) Branching pipe set "DIS-WA1" × 1 (option).
Ṟ
: Pipe of O/U~Branch,
ṟ
: Pipe of Branch~I/U
Adapted to
RoHS
directive
(7) Wall mounted type (SRK)
(a) Twin type
b
PCA001Z611
Summary of Contents for FDC Series
Page 95: ... 94 12 PAC T 173 Models FDT100VF 125VF 140VF H H H H H C B A F G D G PJF000Z285 ...
Page 98: ... 97 12 PAC T 173 Models FDEN60VF 71VF C 2 C 1 A B A B D C 1 C 2 C 1 C 2 E G F B PFA003Z817 ...
Page 113: ... 112 12 PAC T 173 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 278: ... 277 12 PAC T 173 ー K ...
Page 346: ... 345 12 PAC T 173 Power PCB 1BSU OVNCFS 4GRNCEG VJG 2 ...
Page 518: ... 517 12 PAC T 173 3 5 SUPER LINK E BOARD SC ADNA E F SL2NA E and SL3N AE BE to control ...
Page 519: ... 518 12 PAC T 173 ...