 18. MAINTENANCE AND INSPECTION GUIDELINE OF MAIN PARTS OF PACKAGED AIR CONDITIONER

This table indicates the details of regular inspection items and their intervals (inspection 
interval), and the timing of parts replacement under a normal 
use condition. If the equipment falls into a certain category specified by the laws and 
regulations of each country, conduct the maintenance and inspection according to the 
specified rules too. As to the preventive maintenance, the regular inspection interval is 
indicated as the “inspection interval,” and the predicted interval of the “implementation of 
cleaning and adjustment” or “implementation of parts replacement and repair” according 

to the result of the regular inspection is indicated as the “maintenance interval.” As to the 
cleaning and adjustment, the timing is set to prevent the deterioration of parts and the 
degradation of performance. As to the parts replacement and repair after the inspection, the 
timing is set by estimating the operation time or use time, when the wear-out failure period 
is reached.

Note 1)  Random fault is an unexpected failure which occurs before the wear is 

progressed, within the service life of the parts and equipment. It is difficult to 
establish a technological measure against the random fault. At the moment, 
statistical handling is the only measure against the random fault.

Note 2)  The elapsed year marked with * assumes the operating time as 10 hours/day and 

2500 hours/year in a normal operating condition without frequent start/stop. This 
may vary according to the operating condition. Please check the calculation basis 
of the elapsed year when making a maintenance contract.

Note 3) 

 illustrates the estimated timing when the wear-out failure starts 

and how the failure rate increases as the time passes.

Note 4)   The inspection timing of filter is basically every week. However, the contamination 

state varies depending on the type of filter and the use condition. Therefore, 
conduct the inspection in arbitrary cycles according to the use condition.

[Mainly 

indoor

 parts and built-in components] 

*The distinction between the indoor and outdoor assumes the air conditioner for a store and a multiple-air conditioner for a building. This may vary depending on the configuration of the unit, such as equipment air conditioner.

Part Name

Regular Inspection

Preventive Maintenance*

Remarks

Part Name

Details of Inspection

Inspection Method

Criteria <Standard>

Details of Maintenance

Inspection 

Interval

Maintenance Interval

(Used Hours/Duration)

Elapsed Years

1

2

3

4

5

6

7

8

9

10 11 12 13 14 15

Structural 
component

Decorative panel 

(design part)

-  Check of dirt and scratch 

Visual inspection

-  There should be no extreme dirt, scratches, or 

deformation

-  Cleaning with neutral detergent, paintwork by repair 

coating

Every year

Before the air 

conditioning 

season

8 years

Cleaning object item

Intake/outlet grills

-  Visual check of dirt and scratch

-  Outlet grill louver operation check

Visual inspection

-  There should be no extreme scratches or deformation

-  Repair or replace it if deformed or damaged

-  Replace the bearing, motor, etc. when malfunctioning

8 years

Frame, bottom plate, 

etc.

-  Check of rust and peeling off of the heat insulation 

material

-  Check of peeling off and 

fl

 oating of paint coating

Visual inspection

-  There should be no extreme rust or damage of heat 

insulation material

-  If the heat insulation material is peeled off, repair and 

stick it

-  Paintwork by repair coating

8 years

Cleaning object item

Vibration-proof rubber -  Check of deterioration and hardening of rubber

Visual and audible 

inspection

-  Vibration insulation function should not be impaired

-  Replace it when deteriorated or hardened

10 years

Ventilation 
system parts

Filter

-  Visual check of dirt and breakage

Visual inspection

-  Filter material should be seen through

-  There should be no breakage or deformation

-  Clean it if it is dirty

-  Replace it if it is broken

Every week 

Note 4

5 years

Consumable 

components

Fan

Fan casing

-  Visual check of vibration and balance

-  Check of dust adhesion and appearance

Visual inspection

Visual inspection

-  Should not be in an extremely vibrating condition

-  There should be no extreme rust or deformation

-  Replace it in case of vibration and extreme unbalance

-  Clean with a brush or wash with water in case of 

extreme dust adhesion

Every year

Before the air 

conditioning 

season

13 years

Fan motor

-  Sound audibility check

-  Insulation resistance measurement

Audible inspection

500 V mega

-  There should be no abnormal sound generation

-  The resistance value should be 1 M

Ω

 or more

-  When a bearing sound is loud, replace the bearing

-  When the resistance value is 1 M

Ω

 or less, replace the 

motor

20,000 Hr

Bearing

-  Regular lubrication is required

Audible inspection

-  There should be no abnormal sound generation

-  Replace parts regularly

15,000 Hr

Consumable 

components

Automatic louver 

motor

-  Insulation resistance, abnormal sound generation

500 V mega, audible 

inspection

-  The resistance value should be 1 M

Ω

 or more, there 

should be no abnormal sound

-  Replace it if the resistance value is 1 M

Ω

 or less

20,000 Hr

Drain system 
parts

Drain pan

-  Check the clogging of foreign matters and the 

fl

 ow of 

drain water

-  Check of peeling off and 

fl

 oating of paint coating

Visual inspection

-  There should be no drainage clogging

-  There should be no abnormal rust generation and hole 

opening

-  Cleaning of drain pan, inclination check

-  Repair coating or replace the drain pan depending on 

the problem level

8 years

Cleaning object item

Drain pump

-  Check the drainage condition

-  Check the clogging and dirt of the water supply and 

drainage outlet

- Insulation resistance

Visual inspection

Visual inspection

500 V mega

-  Should be drained normally

-  There should be no clogging or dirt

-  The resistance value should be 1 M

Ω

 or more

-  Replace it in case of drain defect

-  Clean it in case of clogging and dirt

-  Replace it if the resistance value is 1 M

Ω

 or less

20,000 Hr

Dewing preventing 

heater

-  Insulation resistance, appearance check

500 V mega, visual 

inspection

-  The resistance value should be 1 M

Ω

 or more, there 

should be no abnormality

-  Replace it if the resistance value is 1 M

Ω

 or less

20,000 Hr

Float switch

-  Operation check

Tester

-  ON-OFF should operate normally

-  Replace it in case of malfunction

20,000 Hr

Refrigerant 
system parts

Air heat exchanger

-  Check the clogging and damage due to foreign objects

- Gas leakage

Visual inspection

Gas detector

-  There should be no clogging or damage

-  No leakage should be detected

-  Wash the air in

fl

 ow side in case of clogging

-  Repair or replace it when gas leakage is detected

5 years

Cleaning object item

Due to atmospheric dirt

Piping in the unit

-  Sympathetic vibration, contact, and corrosion of the 

piping in the unit

-  Sympathetic vibration and contact of capillary tube

Visual inspection

Visual inspection

-  There should be no abnormal sympathetic vibration, 

sound, or corrosion

-  There should be no abnormal sympathetic vibration or 

contact wear

-  Replace it or readjust the piping when extremely 

corroded

-  Replace it or readjust the piping when extremely worn

20,000 Hr

Electronic expansion 

valve

- Operation check

-  Operation sound by power on/off (pressure check)

Tactile inspection

Audible and tactile 

inspection

-  Circulation of refrigerant should be felt

-  There should be driving sound and temperature change

-  Replace it when locking occurs

20,000 Hr

Electromagnetic 

valve, four way 

switching valve, etc.

-  Operation and insulation performances of 

electromagnetic valve, four way switching valve, etc.

-  Corrosion, abnormal sound

500 V mega

Visual and audible 

inspection

-  The resistance value should be 1 M

Ω

 or more

-  There should be no abnormal sound or corrosion

-  Replace it if the resistance value is 1 M

Ω

 or less

20,000 Hr

Electric and 
electronic 
parts

Electric component 

box

(including inverter)

-  Circuit insulation resistance check

-  Terminal part, connector looseness check

500 V mega

Driver, visual inspection

-  The resistance value should be 1 M

Ω

 or more

-  There should be no looseness at the connecting part

-  There should be no deposited foreign matter

-  There should be no abnormal display

-  Clean with a brush in case of extreme dust adhesion

-  Replace it if the resistance value is 1 M

Ω

 or less

-  Retighten or reinsert it if there is looseness

25,000 Hr

Switching power 

source transformer

-  Output voltage measurement

Tester

-  Output voltage should be within a speci

fi

 ed value

-  Replace it if there is voltage abnormality

10 years

Temperature sensor

Humidistat

-  Open, short circuit, earth, appearance check

Tester, visual inspection

-  Should be of a speci

fi

 ed resistance value

-  There should be no cracking or discoloration

-  Replace it in case of disconnection and short circuit

5 years

Remote control switch -  Check the controllability by the operation

Visual inspection

-  LCD should display as operated

-  Replace it in case of failure of the following capability of 

control and the display

25,000 Hr

Explanation of symbols

:  Conduct the cleaning and adjustment according to the inspection result

:  In case of abnormality after inspection, replace or repair the corresponding part.

:  Conduct the periodic replacement (consumable components)

: Random failure

 :  Wear-out failure

PGA012A413_EN.indd   30

PGA012A413_EN.indd   30

2022/6/23   13:25:38

2022/6/23   13:25:38

Summary of Contents for FDC-VNA-W Series

Page 1: ...NGLISH MANUEL DE L UTILISATEUR ANWENDERHANDBUCH DEUTSCH ISTRUZIONI PER L USO ITALIANO MANUAL DEL PROPIETARIO ESPAÑOL GEBRUIKERSHANDLEIDING NEDERLANDS РУКОВОДСТВО ПО ЭКСПЛУАТАЦИИ U MANUAL DO UTILIZADOR PORTUGUÊS РУССКИЙ TÜRKÇE FRANÇAIS KULLANIM KILAVUZU Please refer to the manual provided with WIRED REMOTE CONTROL RC EX series and WIRELESS REMOTE CONTROL RCN E2 series Veuillez vous référer au manue...

Page 2: ...PGA012A413_cover indd 2 PGA012A413_cover indd 2 2022 6 22 16 43 46 2022 6 22 16 43 46 ...

Page 3: ...tion The specified prohibited item is described in the triangle The left mark means Shock hazard alarm marks mean prohibited items The specified prohibited item is described in the circle or in the vicinage marks mean compulsory action or instruction The specified prohibited item is described in the circle The left mark means Earth is needed The user s manual should be read carefully There is info...

Page 4: ...ithout supervision This unit should be installed in rooms which exceed the floor space specified in installation sheets of indoor outdoor unit Refer to the installation sheet INSTALLATION PRECAUTIONS WARNING Make sure to have the installation done by your dealer or a specialist If you install by yourself and the unit is not properly installed water leakage electric shock fire and injuries caused b...

Page 5: ...detergent is dropped on the electric component or motor it may lead to failure smoking or ignition Do not place a burning appliance where the air flow from the unit is directly blown It may cause the imperfect combustion of the equipment Make sure that the unit installation foundation is not damaged due to long term use If it is left to stand the unit may fall down causing injury Do not wash the u...

Page 6: ...hout fault If it is required to relocation and reinstall the unit consult your dealer or a specialist Improper installation of air conditioning unit may cause water leakage electric shock and or fire Do not use the unit where powder or fiber is floating Fine powder or fiber passing through the air filter may stagnate inside the unit and lead to electric leak or short circuit Do not place objects u...

Page 7: ...central control Optional is running When the periodical inspection is necessary page 24 During the ventilation operation page 15 When filter sign is up page 23 When the Permission Prohibition setting is made When the peak cut timer is set page 12 When the weekly timer is set page 19 3 Menu button When setting or changing other than the following 4 8 tap the menu button Then menu items are displaye...

Page 8: ...fer to the installation manual Please refer to the installation manual Please refer to the installation manual Please refer to the installation manual Main menu Run 7 Stop 7 Change operation mode 7 Change set temp 7 Change flap direction 8 Change the fan speed 8 F1 F2 switch operation 8 High power operation 9 Energy saving operation 9 Timer 17 Set ON timer by hour 18 Set OFF timer by hour 18 Set O...

Page 9: ...ion because operation modes are not matched 1 When Heating including auto heating is selected for Operation mode while using an OU for cooling only 2 When Heating is selected for Operation mode while controlling multiple units including units allowed for both cooling and heating and units for cooling only 3 When different operation modes are selected between IUs which are connected to a OU that do...

Page 10: ...he display returns to the TOP screen Swing Stop Changing the function of the F1 or F2 switch can be performed with the F1 F2 function setting The following functions are set as factory settings You may change these settings as desired F1 switch High power operation F2 switch Energy saving operation You can set any of the following functions to the F1 and F2 switches The F1 F2 switches act as short...

Page 11: ...50 Mon F1 High power Timer In operation for high power Set temp F2 Energy saving 1 Push the F1 F2 switch to start the energy saving operation Operation will start even if you press the F1 F2 switch while the unit is stopped Energy saving operation is only allowed when Heating Cooling or Auto is selected for the operation mode Message In operation for energy saving is displayed on the screen during...

Page 12: ...ting operable not operable 1 Tap the Menu button on the TOP screen Main menu screen is displayed When a desired menu item is tapped setting screen for each item is displayed When there are two or more pages the Next button is displayed at the leading page and the Previous button is displayed at the last page The Next and Previous buttons are displayed on pages in between 2 When the Next button is ...

Page 13: ...aving setting Administrator settings The administrator password is provided so that these operations and settings are restricted to administrators managers only such as the owner of the building For the administrator password at the factory setting refer to the Installation Manual When your administrator password is forgotten initialize the password by referring to the Installation Manual Advice I...

Page 14: ...k cut timer Select the day of the week Invalid Setting Tap box below day of week If invalid is selected timer won t start All Disable Mon Tue Wed Thu Fri Sat Sun Back 3 1 5 Screen to check contents of current setting is displayed When the contents are changed or new setting is added select a 1 setting line No and tap the 2 Change button 6 Detail setting screen for the timer setting contents is dis...

Page 15: ...k cut is the higher the effect of energy saving becomes Tap the Set button after the setting 10 Peak cut timer Set Back Tap to set peak cut tap Set Wed No 1 Peak cut 7 00 AM 8 00 AM 8 00 AM 8 00 PM 7 00 AM 7 00 PM 3 The same setting method as the Setting in the cooling operation can be applied to the Setting in heating 2 Set desired time and temperature with the buttons When the Set button is tappe...

Page 16: ... is displayed during Operation wait Complete stop The air conditioner stops and does not resume operation even when a person returns When Complete stop is executed In auto off mode disappears and the operation lamp turns off To resume operation press the Run Stop switch 3 Use the button to set the temperature and tap the Set button Temporarily determine the set temperature The allowable range is a...

Page 17: ...t the item Initial settings Clock setting Date time display Summer time Contrast Backlight Next Back Select the item 1 Tap the Menu button on the TOP screen and select User setting Initial settings Clock setting 2 The Clock setting screen is displayed Set the dd mm yy with the buttons Tap the Time button after the setting The clock setting is necessary for the following settings Peak cut timer Set...

Page 18: ...OP screen and select User setting Initial settings Contrast Contrast Back Set Adjust Dark Bright Upper Lower Contrast Back Set Adjust contrast between upper and lower Dark Bright 1 Tap the Menu button on the TOP screen and select User setting Initial settings Backlight 3 Tap the Set button after the setting 2 The Backlight setting screen is displayed Tap the ON or OFF buttons for the backlight lig...

Page 19: ...tivate whenever any operation starts Set ON timer by hour page 18 When the set time elapses the air conditioner starts Operating conditions at the start of operation can be set Operation takes place once at each setting Set OFF timer by hour page 18 When the set time elapses the air conditioner stops Operation takes place once at each setting Set ON timer by clock page 19 The air conditioner start...

Page 20: ...ion at the last action 4 Cooling Set ON timer by hour Set Back Set temp Select the item to change Details Previous Warming up Set ON timer by hour Set Back hours Tap to set clock time tap Set A C will start at the set hours later Cancel Next Cooling Set ON timer by hour No setting Back Please select operation mode Fan Heating Dry Auto 7 Tap a desired fan speed If the No setting button is tapped it...

Page 21: ...N timer by clock Set Back Once Tap to set clock time tap Set A C will start at the set clock time Cancel Next AM Set OFF timer by clock Set Back Once Tap to set clock time tap Set A C will stop at the set clock time Cancel AM The Clock setting page 15 must be made when the weekly timer is used The weekly timer can be set from the main R C only Advice 1 Tap the Menu button on the TOP screen and sel...

Page 22: ...t operate on the day set as holiday Two or more holidays can be set To enable the timer on the day set as holiday it is necessary to reset the holiday setting When tapping 3 All Disable button the timer does not operate on all days of the week When the timer is used be sure not to set All Disable 5 Screen to check contents of current setting is displayed When the contents are changed or new settin...

Page 23: ...ay changes to a day of the week setting check screen after saving 3 When making the setting after changing a day of the week repeat the setting from the step 3 Weekly timer No setting Back Select the fan speed Auto Select a line tap Change Change Weekdays Weekly timer State Enable Enable Enable Enable Type Time Enter Back Next ON ON ON OFF Mode Fan Temp Auto Auto Weekly timer Yes Back Do you want ...

Page 24: ...put screen is displayed Enter the administrator password 2 The Silent mode control Start End screen is displayed Tap the Start button to start the silent mode control To terminate the silent mode control tap the End button 3 During silent mode control Outdoor unit silent mode control ON will be displayed on the message display Silent mode control will not be disabled even if you press the Run Stop...

Page 25: ...ct Filter Filter sign reset You can also use the F1 and F2 switches to perform this operation Set the filter sign reset to the F1 F2 switch using the Switch function to perform this operation In order to announce the time for cleaning of the air filter the message of Filter cleaning Touch here is displayed when the cumulative operation time of the IU reaches the preset time After you clean the fil...

Page 26: ...ving Direction The message Standby Wait a while may be displayed maximum of 30 minutes on the R C during the first operation following a breaker power on or power loss This does not indicate a failure it is caused by the cooling machine oil protect control that is activated in order to protect the compressor Please wait until the message Standby Wait a while disappears Standby Wait a while display...

Page 27: ...ower F2 Energy saving Timer In operation for heating standby Set temp Direction Menu Cooling 20 20 Tue F1 High power F2 Energy saving ON In operation for warming up Set temp Direction This does not indicate a failure the message indicates that the unit is controlled through a central control device Operations allowed during central control Filter sign reset Administrator settings Invalid request C...

Page 28: ...ted to the product the message There is a information of maintenance Check the content from Menu may be displayed in the message display When this message is displayed tap the Menu button The maintenance description will be displayed Contact the dealer company shown as the Contact company page 24 and notify the details code of required maintenance There is a information of maintenance Check the co...

Page 29: ...p it or use cleaner If it is very dirty dissolve some neutral detergent in lukewarm water approximately 30 C rinse the filter with it and wash the detergent away completely 2 After the air filter is dried mount it to the main body and press RESET button ATTENTION Do not dry by exposing the air filter to the direct sunlight or using fire Otherwise the filter may be damaged Do not operate the air co...

Page 30: ... Is sunlight or other strong illumination striking the receive unit wireless unit ON OFF Is the air filter clogged Is the swing louver horizontal during heating If the swing louver is horizontal the air flow may not reach down to the floor Are there any obstacles blocking the air inlet and outlet grill Is the direct daylight coming into the room Are there any unexpected heat sources in the room Ar...

Page 31: ... case of exposed wiring is the wiring fixed with the attached screw Is the attached remote control clamps used for fixing the remote control cord Is the remote control mounted at a height where children cannot reach ELECTRICAL WORK RELOCATION INSPECTION MAINTENANCE Please use the system in the following operation range If the system is operated outside this range the protection controls may be act...

Page 32: ...tion The resistance value should be 1 MΩ or more When a bearing sound is loud replace the bearing When the resistance value is 1 MΩ or less replace the motor 20 000 Hr Bearing Regular lubrication is required Audible inspection There should be no abnormal sound generation Replace parts regularly 15 000 Hr Consumable components Automatic louver motor Insulation resistance abnormal sound generation 5...

Page 33: ... atmospheric dirt Piping in the unit Sympathetic vibration contact and corrosion of the piping in the unit Sympathetic vibration and contact of capillary tube Visual inspection Visual inspection There should be no abnormal sympathetic vibration sound or corrosion There should be no abnormal sympathetic vibration or contact wear Replace it or readjust the piping when extremely corroded Replace it o...

Page 34: ...it is loose Clean with a brush in case of deposited foreign matter adhesion 25 000 Hr Electrical component including boards etc HIC board short circuit check Visual check of dirt adhesion to the board etc Self diagnosis mode appearance check Tester Visual inspection Visual inspection Should be of a specified resistance value There should be no deposited foreign matter There should be no abnormal d...

Page 35: ...ries FDC VSA W Series Category FDF Series UK DECLARATION OF CONFORMITY We MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS LTD 2 3 Marunouchi 3 chome Chiyoda ku Tokyo 100 8332 Japan declare under our sole responsibility that the apparatus referred to in this declaration conforms with the following directives Description of apparatus Split Type Air Conditioner Model name Relevant GB Directives Supply of...

Page 36: ...g 238 Luna ArenA 1101 CM Amsterdam Netherlands P O Box 23393 1100 DW Amsterdam Netherlands Tel 31 20 406 4535 http www mhiaeservices com MITSUBISHI HEAVY INDUSTRIES AIR CONDITIONERS AUSTRALIA PTY LTD Block E 391 Park Road Regents Park NSW 2143 PO BOX 3167 Regents Park NSW 2143 Tel 61 2 8774 7500 Fax 61 2 8774 7501 https www mhiaa com au MITSUBISHI HEAVY INDUSTRIES MAHAJAK AIR CONDITIONERS CO LTD 2...

Reviews: