104
–
'14 • KX-SM-200
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor unit
Heat source unit
Content
E46
E46
Mixed address setting methods
coexistent in same network
Keeps flashing
Stays OFF
Keeps flashing
Stays OFF
1. Applicable model
5. Troubleshooting
Heat source unit
Diagnosis
Countermeasure
NO
Reset power source and restart.
If signal line is connected to more than
2 heat source unit systems, address setting
should be done by manually.
YES
Isn't the
signal line of a heat source
unit system applying automatic
address setting connected to
other heat source unit
system?
YES
NO
Does E46 recur?
YES
Turn ON the power of each heat source unit
one by one and search the heat source unit
that can start up with automatic address
setting.
NO
Is E46 still displayed?
Save data for 30 minutes before stopping in Mente PC.
Check and save the data of
operating conditions.
Check the address setting
method of faulty network
whether it is automatic
setting or manual setting.
Test run.
* No action is taken
because it is judged
that the power reset is
not done after changing
address.
Correct signal line.
*In case of automatic
address setting, signal
line cannot be connected
to other heat source unit
system.
Test run.
Replace heat source unit
control PCB*.
(Rotary switch anomaly)
* Before replacement,
please confirm whether
the rotary switch for
address setting is not
damaged.
(It was experienced that
No.5 on rotary switch
was not recognized )
2. Error detection method
If the signal line of a heat source
unit system applied automatic
address setting is connected to
other heat source unit system.
(Detected at indoor unit side)
3. Condition of error displayed
Same as above.
4. Presumable cause
• Mistake in the address setting
• Mistake in the connection of
signal wire
Note:
After completing the above procedure, reset the power and confirm that the error display does not recur. Unless the power
is reset for both indoor unit and heat source unit, the set addresses will not be confirmed.
Caution:
Unless the power is reset after changing
address, the set address will not be
confirmed.
<Reference>
Error display at mixed address setting
Auto
Manual
Auto address setting
E31
E46
Manual address setting
E46
Normal