111
–
'14 • KX-SM-200
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor unit
Heat source unit
Content
E61
E61-1, 2 *1
Communications error between
the master unit and slave units
Keeps flashing
Stays OFF
Keeps flashing
*1
1. Applicable model
5. Troubleshooting
Heat source unit
Diagnosis
Countermeasure
Is E61 occur?
Reset the power source and restart operation.
NO
NO
YES
YES
Is the
address setting of master
and slave heat source units
OK?
Correct.
Replace the heat source
unit PCB.
Anomalous noise, etc.
2. Error detection method
E61 is displayed on 7-segment
LED.
3. Condition of error displayed
When the communication
between master unit and slave
units is not established.
4. Presumable cause
• Signal wire anomaly
• Heat source unit control PCB
anomaly
• Inverter PCB anomaly
• Rush current prevention
resistor anomaly
Note:
*1 E61-1/1-time flash: Slave unit 1, E61-2/2-time flash: Slave unit 2