'14 • KX-SM-200
Indoor unit condition
Cooling
Heating
Run
Thermo
off
Stop
Stop
Thermo
off
Run
Operation
pattern
Account
○
(○) (○)
×
×
×
C6
C6
×
×
×
(○) (○)
○
E6
E6
All cooling operation
All heating operation
Low pressure under high water
temperature condition
Operation pattern
Water heat exchanger condition
Condenser
Evaporator
Compressor control
Low pressure control
High pressure control
ON
20SM
20SH
EEVW
EEVSC
EEVG
SVR
SVB
SVO
OFF
4 way valve
OFF
ON
Electronic expansion valve for
water heat exchanger
Fully open
SH control
Electronic expansion valve for
sub-cooling
SH control / Td control
Pressure valve for receiver
High pressure control
Fully closed
Decompression valve for receiver
OFF(/ON)
OFF(/ON)
Solenoidvalveforhot-gasbypass
ON/OFF
Solenoid valve for oil return
ON/OFF
Notes : Operations may differ from the above during the protective control, or other.
1.4 Operation control function by the heat source unit control
(A) Normal control
(1) Basic controls in each operation pattern and roles of functional components
Z
ESP-FP-2090
(2) Heat source operation mode
On the standard models of pipe system, the heat source unit operation mode of Stop/Cooling/Heating is selected based on
the information of indoor units, and then respective controls are performed.
<Contents of control>
(a)
Determination of heat source unit operation mode
Operation mode of heat source unit is determined based on respective signals of Operation/Stop and Cooling/Heating.
The compressor, however, starts only upon confirmation of the start of water pump.
(b)
Type of heat source unit operation mode
1)
Heat source unit operation mode - Stop
)
Heat source unit operation mode - Cooling (C)
)
Heat source unit operation mode - Heating (E)
(c)
Priority in operation mode selection.
1)
First priority is given to the forced cooling/heating operation.
)
Second priority is given as follows
Priority in the operation mode selection can be changed using the -segment setting [P01].
P01 setting
Mode
0 (Factory default)
First unit’s operation mode
1
Last unit’s operation mode
・
First unit’s operation mode: Operation mode of the indoor unit which is operated first time after stop of the heat
source unit operation mode
・
Last unit’s operation mode: Operation mode of the indoor unit which is operated at the last time