'14 • KX-SM-200
(d) Forced cooling /heating operation (Master unit)
(Note) Following explanation is based on using CnG1 terminal and setting function [P0]-[] with -segment display.
However other terminals can be used with following function setting of -segment display.
CnS1: [P0]-[]
CnS: [P0]-[]
CnG:
[P10]-[]
1) When SW- on the heat source unit control PCB is turned ON after setting function [P0]-[] with -segment dis-
play, if CnG1 is shorted, forced heating operation is performed, but if CnG1 is open, forced cooling operation is per-
formed.
2) If the different mode from the forced operation mode is commanded from indoor unit, the "mode unmatch" message
is displayed on the LCD of remote control and the operation is entered in FAN mode.
(3) Emergency stop control
When one of indoor units receives the emergency stop signal through CnT terminal on the indoor control PCB from the device
like as refrigerant leakage detector and that information is transmitted to the heat source unit, the heat source unit stops opera-
tion and emergency stop error message transmitted to all indoor units running.
It is able to make the emergency stop function effective by remote control indoor function setting.
(a) When the heat source unit receives the “Emergency stop” command from the indoor unit, it makes all stop by error.
(b) And the “Emergency stop” command is transmitted to all indoor units and error code “E” is displayed.
(c) When the heat source unit receives the “Emergency stop reset” command from the indoor unit, the “Emergency stop reset”
command is transmitted to all indoor units.
SW-
ON
CnG1
Open
Operation in cooling only
Shorted
Operation in heating only
OFF
Normal operation
(4) Compressor control (Master unit/slave unit)
(a) Starting compressor
(i) Compressor starting order
After turning the power on, firstly compressor starts. And corresponding to the condition of under-dome temperature
and to the required capacity of indoor units thermostat ON, the next compressor will start sequentially, and finally
maximum compressors ( in case of heat source units combination use) will start simultaneously.
1) Single use (Model 224, 280, 335)
CM1
Range of the compressor operation speed relative to load is as follows.
System load range
(Number of operating heat source units)
0
1
Local load range
(Number of compressors operating in heat source units)
0
1
CM1
0rps
20−120rps