'14 • KX-SM-200
(1) External input and demand input (Master unit/Slave unit)
(a) Operation permission or prohibition mode
(Note) Following explanation is based on using CnS1 terminal and setting function [P07]-[0] with 7-segment display.
However other terminals can be used with following function setting of 7-segment display.
CnS2: [P08]-[0]
CnG1: [P09]-[0]
CnG2: [P10]-[0]
1)
Operation permission or prohibition mode is switched with the connector (CnS1) and the Jumper wire (J13) on
the heat source unit control PCB after setting function [P07]-[0] (Factory setting) with 7-segment display
(B) Option controls
• External input terminal
①
4 External input terminals (CnS1, CnS2, CnG1 and CnG2) are provided. (See Fig-1)
②
Each external input terminal can be changed its function by allotting the external input function No. of P07-P10 selected
with 7-segment respectively. (External input functions of the code P07-P10 are shown in Fig-2)
③
The following function is effective, when the external input function of PXX-"X" is allotted and the signal is input to the
external terminal of CnXX.
(Example) If CnS1 terminal is used for demand control (pulse input), allot the "1" of P07 and open J13, and if CnS2 terminal is
used for demand control (level input), allot the "1" of P08 and short J13.
④
J13: Switching of CnS1,S2 input method (CnS1, S2 only)
J13 shorted: Level input by CnS1, S2
J13 open : Pulse input by CnS1, S2
*1 "Setting" means;
Master : Set only the master unit. (No necessary to set the slave unit)
Master/Slave: Set both master/slave unit same.
External input terminal
External input function allotment of 7-segment
Terminal
Specification
Factory setting
Code
Function No.
Factory setting
CnS1
No voltage contact (DC12V)
Shorted
P07
"0"-"9"
"0"
CnS2
No voltage contact (DC12V)
Shorted
P08
"0"-"9"
"1"
CnG1
No voltage contact (DC12V)
Open
P09
"0"-"9"
"2"
CnG2
No voltage contact (DC12V)
Open
P10
"0"-"9"
"3"
Fig-1
*1 According to the demand setting table.
“0” : External operation input
“1” : Demand input *1
“2” : Cooling / heating forced operation input
“6” : Test run external input 1 (SW5-1 equivalent)
“7” : Test run external input 2 (SW5-2 equivalent)
“9” : 2-step demand input *1
“12”: Building multi energy save control
Permitted
Heating
Test run start
Cooling
Valid
Prohibited
Cooling
Normal
Heating
Invalid
By changing the allocation of external input function (P07-10) on the 7-segment, functions of external input terminal
may be selected. Inputting signals to external input terminals enable the following functions.
Demand
control
Function
assignment 1
Function
assignment 9
None (Normal)
1-step
2-step
Shorted
Open
Open
Shorted
Shorted
Open
*1 Demand setting table
Setting value for external input function assignment
External input terminal shorted
External input terminal open
Fig-2
Invalid
Valid
Invalid
Valid