'14 • KX-SM-200
(3) Test run
(a) This control can be performed from the master unit, not from the slave unit.
If this control is done from the slave unit, the following display is shown on the -segement display.
The display returns to normal display if the test run control switch is reset.
(b) Test run from master heat source units with dip switches SW5-1 and SW5-2.
Take note that this operation has priority over other option devices such as central control and etc.
This operation status is transmitted to the option devices.
(Note) Test run operation by external input is also available with following method. (Refer next page for detail)
• Select the external input terminal (CnS1) and set -segment [P11]-[] for the function of SW-1, and select the external input terminal (CnS) and
set -segment [P1]-[] for the function of SW-.
• Other combination of external input terminals (CnS1, CnS, CnG1, CnG) and of setting function with -segment ([P11], [P1], [P1], [P1] and
-[], -[]) are avilable to use.
(c) Starting conditions of test run operation
(i) Dip switch SW-1 is turned ON. However the input before the power ON is invalid.
(ii) The dip switches SW and SW, other than SW-1and SW-, should be turned OFF.
However, regarding the dip switch SW- for automatic backup operation, it is invalid during test run operation
regardless whether SW3-2 is turned ON (valid) or OFF (invalid).→In order to check trouble during test run operation.
(d) Control during test run (If indoor units are normal)
(i) Heating operation is performed with SW- OFF, while cooling operation is performed with SW- ON.
(ii) Indoor EEV control at the end of test run is depended on the specifications of the indoor unit.
(iii) Cooling operation: Compressor frequency control is depended on the cooling low pressure control.
(iv) Heating operation: Compressor frequency control is depended on the heating high pressure control.
(e) Ending conditions of test run operation
Test run operation is terminated if one of following conditions is satisfied.
(i) Test run operation ends when the dip switch SW-1 is turned OFF.
(ii) When the operation is stopped by the error control during test run, the error is displayed same as the normal operation
and the state of error stop is retained even if SW-1 is turned OFF.
Code indicator
Data indicator
Contents of invalid operation
10
OPE
Slave setting is invalid.
ON
SW5-1
SW5-2
OFF
ON
OFF
Test run for heating
Test run for cooling
Normally operation and after test operation
CnS1
Shorted
CnS
Open
Test run for heating
Shorted
Test run for cooling
Open
Normal operation and after test operation