0
–
'14 • KX-SM-200
-
3
-
Code
No.
Remarks
Contents of display
Data display
range
Minimum
unit
C00
C02
C03
C04
C07
C10
C12
C14
C15
C16
C18
C20
C21
C22
C23
C25
C26
0~130
L,-20~70
L,-40~75
L,-40~75
L,-20~140
L,-30~90
L,-20~140
L,-40~75
L,-40~75
L,-40~75
0~50
0~500
0~500
0~500
0~500
0~4.15
0~1.70
1Hz
1°C
1°C
1°C
1°C
1°C
1°C
1°C
1°C
1°C
1A
1Pulse
1Pulse
1Pulse
0.01MPa
0.01MPa
Tho-A Atmosphere air temp.
Tho-R1 Heat exchanger temp. 1
Tho-R2 Heat exchanger temp. 2
Tho-D1 Discharge pipe temp. (CM1)
Tho-C1 Under-dome temp. (CM1)
Tho-P1 Power transistor temp. (CM1)
Tho-SC Sub-cooling coil temp. 1
Tho-H Sub-cooling coil temp. 2
Tho-S Suction pipe temp.
CT1 Current (CM1)
Opening angle of EEVSC expansion valve for
sub-cooling coil
PSL Low pressure sensor
CM1 operating frequency
[Exx]
[oPx][oPE-X]
[PdS][PdE]
[CH ][CHF][CO ][HE ][PCL][dLP]
PSH High pressure sensor
C30
0,1
63H1-1
í
Order of 100 : 63H1-1
Order of 10 : Spare
(0: Close, 1: Open)
'14 • KX-SM-200
Opening angle of EEVW1 expansion valve for
water heat exchanger 1
Opening angle of EEVW2 expansion valve for
water heat exchanger 2
Opening angle of EEVG expansion valve for
high pressure control
1Pulse
C27
0~50
1A
Inverter secondary current 1
C29
0~4.15
0.01MPa
PSLQ Liquid pipe pressure sensor
Order of 1 : Spare
C31
0,1
CNS1
í
Order of 100 : CNS1
Order of 10 : CNS2
(0: Close, 1: Open)
Order of 1 : CNG1
C32
0,1
CNG2
í
Order of 100 : CNG2
Order of 10 : SVA
(0: Close, 1: Open)
Order of 1 : Spare
C33
0,1
CH1
í
Order of 100 : Spare
Order of 10 : Spare
(0: Close, 1: Open)
Order of 1 : CH1
CNS2
CNG1
SVA
Unusual
Warning
Special
code
code
code
< Information for sensor or actuator value >
< Operation information >
Summary of Contents for FDC1000KXZWE1
Page 171: ... 14 KX SM 200 169 ...
Page 172: ... 14 KX SM 200 170 ...
Page 173: ... 14 KX SM 200 171 ...
Page 174: ... 14 KX SM 200 172 ...