'14 • KX-SM-200
-
6
-
Code
No.
Remarks
Contents of display
Data display
range
Minimum
unit
P30
P31
P32
P33
P34
0, 1
—
—
1
1
—
Superlink communication status
Start automatic address setting
Input starting indoor address
Input the number of connected indoor units
Polarity definition
< New Superlink setting >
0: Current Superlink
1: New Superlink
0: Automatic address setting standby
1: Automatic address setting start
0: Network polarity not defined
1: Network polarity defined
0: (Factory default)
0, 1
0: (Factory default)
1~127
24: (Factory default)
1~24(*)
Specify the starting indoor address connected in one refrigerant system
for automatic address setting.
Specify the number of indoor units connected in one refrigerant system
for automatic address setting.
(*) Maximum connectable number of indoor units for each heat source unit
'14 • KX-SM-200
0: (Factory default)
0, 1
[C66] Control status
<Definition of signal>
Shows the status of control in operation currently.
If two or more controls among the following protection controls are established simultaneously, No. of the control of which number
is larger is displayed.
Protection control status
Number
Ordinary control
Remote control all stop
0
Operating control
Ordinary heating control
1
2
10
Oil return control
Defrost control
11
12
13
14
15
16
20
21
22
26
27
28
Ordinary cooling control
Test run control
Pump down control for replacement
Demand control
Special control
Pump down control at start/stop
Indoor heat exchanger refrigerant purge control
Heat source unit heat exchanger refrigerant purge control
Oil equalization rotation control
Oil equalization control
Low outdoor temperature control
Cooling unusual low pressure return control
Compressor dilution protection control