–
60
–
'14 • KX-SM-200
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor unit
Heat source unit
Content
None
–
Operates but does not heat
Keeps flashing
Stays OFF
Keeps flashing
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
NO
YES
YES
NO
YES
YES
YES
NO
NO
NO
YES
NO
Check the indoor fan operation.
Check the temperature difference between
return and suction air of indoor unit.
Mistake in model selection.
Calculate heat load once more.
Check following operation control function.
. Control for determine compressor rotation speed
. Protective control by controlling compressor
rotation speed
Which control is appropriate to this phenomenon.
The unit is operating normally, but is operating
under the protective control of compressor or
other respective components.
Is the
temperature difference
between return and
suction air 10-30° at
heating?
Does the
heat load increase after
installation?
Is the compressor
operating?
Is the
compressor rotation
speed low?
Is the
operating conditions of
indoor/heat source unit
under rated condition?
" WAIT "
message is displayed [for
3 seconds] when performing
cooling, dehumidifying or heating
operation from remote
control?
Note (1) Outdoor: 7ºC
Indoor : 20ºCDB
It is normal.
(This unit is designed
to start in the soft start
mode by detecting the
compressor under-dome
temperature when it restart
after power reset.)
It is necessary to replace to
higher capacity unit or to
install additional unit.
Compressor refrigerant
oil protective control at
starting is activated.
For the contents of control,
refer to the compressor
start control.
Compressor may be
stopped by the error
detection control.
For the contents of control,
refer to anomalous stop
control by controlling
compressor rotation speed
of microcomputer control
function.
Check the followings.
• Minor clogging of filter
• Minor fouling of heat exchanger
• Minor short-circuit of airflow
• Slightly insufficient or excessive
refrigerant amount
• Poor compression of compressor
Check suspicious points
considering appropriate
operation control.
Check the followings for
reference.
• Severe clogging of filter
• Severe clogging of heat
exchanger
• Severe short-circuit of airflow
• Severely insufficient or
excessive refrigerant amount
• Under protective control of
compressor
• Indoor unit fan tap setting
• Valid setting of silent mode
2. Error detection method
3. Condition of error displayed
4. Presumable cause
• 4-way valve anomaly
• Poor compression of
compressor
• Expansion valve anomaly
operation
Note:
Summary of Contents for FDC1000KXZWE1
Page 171: ... 14 KX SM 200 169 ...
Page 172: ... 14 KX SM 200 170 ...
Page 173: ... 14 KX SM 200 171 ...
Page 174: ... 14 KX SM 200 172 ...