71
–
'14 • KX-SM-200
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor unit
Heat source unit
Content
WAIT
–
WAIT
(4)
Keeps flashing
Stays OFF
Keeps flashing Keeps flashing
1. Applicable model
5. Troubleshooting
All models
(In case that is kept
on displaying on the remote
control for more than 2 minutes
after power ON.)
Diagnosis
Countermeasure
NO
Does
heat source unit green LED
keep flashing?
is kept on
displaying on the remote
control for more than 2
minutes after power ON.
Does
heat source unit green LED
keep flashing?
Does
heat source unit red LED flash
2 times?
Are
the wires between indoor
and heat source units
connected properly ?
Is
AC380-415V detected
between L1-L2, L2-L3, L3-L1
respectively at heat source unit
terminal block?
Is
AC220-240V detected
between L-N at indoor
terminal block?
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
A
Refer next page.
WAIT
Indoor control PCB
anomaly
Replace it.
Indoor control PCB
anomaly
Replace it.
Remote control anomaly
Replace it.
Breakage of wires for
remote control
Replace it.
Correct the connecting
wires between indoor and
heat source units.
Heat source unit control
PCB anomaly
Replace it.
Breakage of connecting
wire
Noise.
Indoor control PCB
anomaly
Replace it.
2. Error detection method
3. Condition of error displayed
4. Presumable cause
• Fuse blown
• Noise filter anomaly
• Anomalous connection of
wire between PCBs
• Indoor control PCB anomaly
• Remote control anomaly
• Breakage of connecting wires
of remote control
• Heat source unit control PCB
anomaly
Note:
WAIT
Summary of Contents for FDC1000KXZWE1
Page 171: ... 14 KX SM 200 169 ...