91
–
'14 • KX-SM-200
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor unit
Heat source unit
Content
E30
E30
Unmatch connection of
indoor and heat source unit
Keeps flashing
Stays Off
Keeps flashing 1 time flash
1. Applicable model
5. Troubleshooting
Heat source unit
Diagnosis
Countermeasure
Is the
wiring connection between
indoor and heat source units
correctly?
YES
NO
Is
the voltage
between L1-N at the terminal
block on indoor unit
AC220/240V?
NO
Is the voltage
between L1-L2, L2-L3
and L3-L1 at the terminal block on
heat source unit AC380/415V
respectively?
YES
YES
NO
Correct the wiring
Replace heat source unit
control PCB
Disconnection or breakage
of wire between indoor and
heat source unit
Replace indoor unit PCB
2. Error detection method
3. Condition of error displayed
4. Presumable cause
• Indoor control PCB anomaly
• Heat source unit control PCB
anomaly