'14 • KX-SM-200
Error code
Remote control:
7-segment display:
LED
Green
Red
Indoor unit
Heat source unit
Content
E36
E36-1*1
Discharge pipe temperature
error (Tho-D1)
Keeps flashing
Stays OFF
Keeps flashing
*2
1. Applicable model
5. Troubleshooting
Heat source unit
Diagnosis
Countermeasure
Is the unit
installation environment
within the range of
limitation?
Are the
refrigerant amount and
piping length
OK?
Is the
discharge pipe
temperature thermistor
OK?
Save data for 30 minutes before stopping in Mente PC.
YES
YES
YES
Does the error recur
when restarting?
YES
YES
Is there
DC13V of output
signal for EEVSC from heat
source unit control
PCB?
YES
Is the coil of
EEVSC energized?
YES
Does the
refrigerant flow through
EEVSC main
body?
YES
Is the
insertion of the
thermistor connector into the
connector on heat source unit
control PCB
OK?
Reset the power source and restart operation.
NO
NO
NO
NO
NO
NO
NO
NO
Check and save the data of
operating condition
Check the ROM version
Confirmation of EEVSC
operation
Propose an improvement to
the customer.
Adjust the refrigerant
amount properly.
(Check whether the
refrigerant amount is
insufficient or not.)
(Check the gas leakage)
Insert connector securely.
Check if the characteristics
are correct by referring
the characteristics chart
of E39. And if necessary,
replace the discharge pipe
temperature thermistor.
Check it, as much as
possible, under the
operating conditions for
30 minutes before error
occurred.
Wait and see.
Continue to obtain data, if
possible.
(Keep connecting the
Mente PC)
Replace heat source unit
control PCB.
Replace the coil EEVSC.
Replace the EEVSC
main body. (If there is no
refrigerant in liquid line,
charge refrigerant additional)
Check refrigerant amount
again.
2. Error detection method
When anomalously high
temperature is detected by the
discharge pipe temperature
thermistor (Tho-D1).
3. Condition of error displayed
When 130°C or higher is detected
by the discharge temperature
thermistor, the compressor
stops. After 3 minutes
delay,
the compressor starts again.
automatically, but if this anomaly
occurs 2 times within 60 minutes
after the initial detection, or
130°C or higher is detected
continuously for 60 minutes.
4. Presumable cause
• Discharge pipe temperature
anomaly
• EEVSC (liquid refrigerant
by-pass valve ) anomaly
• Breakage of coil
• Faulty main body.
• Heat source unit control PCB
anomaly
• Insufficient amount of
refrigerant
Note:
*1 E36-1: Tho-D1 *2 E36-1: 1-time flash