130
–
'14 • KX-SM-204
Function of Dip switch for control (SW3, 4, 5)
• SW3 (Function setting)
Function of Jumper wire (J13, 15)
(With: Shorted / None: Opened)
• SW5 (Function setting)
Switch
Function
SW3-1
ON Inspection LED reset
OFF Normal
SW3-2
ON Backup operation
OFF Normal
SW3-4
ON Refrigerant quantity check
OFF Normal
SW3-5
ON Check operation start
OFF Normal
SW3-7
ON Forced cooling/heating
OFF Normal
Jumper
Function
J13
With
External input Level input
None External input Pulse input
J15
With
Defrost start temperature Normal
None Defrost start temperature Cold weather region
• SW4 (Model selection)
Switch
Model
SW4
1
2
3
4
FDC224KXZXE1
OFF
OFF
OFF
OFF
FDC280KXZXE1
ON
OFF
OFF
OFF
FDC335KXZXE1
OFF
ON
OFF
OFF
• SW4 (Master/Slave setting)
Outdoor unit
SW4-7
SW4-8
Master
OFF
OFF
Slave 1
ON
OFF
Slave 2
OFF
ON
ON/OFF
Function
SW5-1
ON
Test run switch
test run
OFF
Test run switch
Normal
SW5-2
ON
Test run operation mode Cooling
OFF
Test run operation mode Heating
SW5-3
ON
Pump down switch
Pump down
OFF
Pump down switch
Normal
SW5-5
ON
Superlink protocol : Previous SL
OFF
Superlink protocol : New SL
• SW7,8,9 (Function setting)
Switch
Function
SW7 Data erase/data write
SW8 7-segment display No. UP
order of 1
SW9 7-segment display No. UP
order of 10