1.4 Operation control function by the outdoor control
(A) Normal control
(1) Operation of major functional components under each operation mode
Functional
Components
Indoor unit fan
Compressor [CM1]
Outdoor unit fan [FMo-1]
Outdoor unit fan [FMo-2]
4 way valve [20S]
Solenoid valve [SV6]
Solenoid valve [SV11]
Electronic expansion valve
for heating [EEVH1, 2]
Electronic expansion valve
for sub-cooling [EEVSC]
Indoor unit electronic
expansion valve
Operation
mode
Cooling
Heating
Defrost
Thermostat OFF
Thermostat ON
Thermostat OFF
Thermostat ON
Fan
Dehumidifying
Remote control
command
Superheating
control response
Outlet temperature
control response
Superheating
Control Response
Fully closed
Fully closed
Slight opening
control
Model-specific
aperture opening
angle
Fully open
※
1
※
3
Fully open
※
3
※
4
Fully closed
※
2
Fully closed
Fully closed
Fully closed
Fully closed
※
2
Superheating
control response
Opening pulse
control
Fully closed
/ Fully open
Opening pulse
control
Remote control
command
Remote control
command
Remote control
command
Intermittent
operation
→
�
/
�
/
�
/
�
�
→
�
→
�
→
�
�
�
/
�
�
/
�
/
�
�
�
�
/
�
Inverter cooling fan
[FMC1]
/
�
/
�
/
�
/
�
�
/
�
/
�
/
�
�
�
�
�
�
�
/
�
/
�
�
�
/
�
�
/
�
�
Solenoid valve [20UF]
/
�
/
�
/
�
/
�
/
�
�
�
�
�
�
Magnetic contactor CM1
[52X1]
�
/
Solenoid valve [SV1]
/
�
�
�
/
�
�
/
�
/
�
Crankcase heater [CH1]
/
�
/
�
/
�
/
�
/
�
/
�
/
�
Notes(1)
�
: ON,
�
: OFF,
�
/
�
,
�
/
�
: ON or OFF
(2)
※
1: The EEVH1, 2 of master unit are fully opened and those of slave unit are fully closed.
(3)
※
2: When the unit is stopped from cooling operation, the EEVH1, 2 of master unit are fully opened and those of slave unit are fully closed.
When the unit is stopped from heating operation, the EEVH1, 2 of both master and slave units are fully closed unless the opening degree is specified
by the low pressure protective control.
(4)
※
3: When the operation mode is changed from heating to cooling/dehumidifying, EEVH1, 2 are maintained at fully closed position and EEV of only one
indoor unit keeps 60 pulse until 20S is turned OFF.
(5)
※
4: When the operation mode is changed from cooling/dehumidifying to heating, EEVH1, 2 are maintained at fully opened position and EEVs of all
indoor units keep 0 pulse until 20S is turned ON.
(6) This shows the state of output when all indoor units are in the same operation mode.