'14 • KX-SM-204
–
24
–
'14 • KX-SM-204
Model 224 (Master) + 280 (Slave)
Master unit
Slave unit
CM01
CM11
(CM1)
(CM1)
Range of the compressor operation speed relative to load is as follows. Following table is applicable when CM01 starts initially.
System load range
0
1
2
Local load range
0
1
1
Master unit
CM01
0rps
21−65rps
31−70rps
Slave unit
CM11
0rps
0rps
52−120rps
5) 2 outdoor units combination use (Model 560, 615, 670)
Master unit
Slave unit
CM01
CM11
(CM1)
(CM1)
Range of the compressor operation speed relative to load is as follows. Following table is applicable when CM01 starts initially.
System load range
0
1
2
Local load range
0
1
1
Master unit
CM01
0rps
20−65rps
31−120rps
Slave unit
CM11
0rps
0rps
31−120rps
6) 3 outdoor units combination use (Model 735)
Master unit
Slave unit 1
Slave unit 2
CM01
CM11
(CM1)
CM21
(CM1)
(CM1)
Range of the compressor operation speed relative to load is as follows. Following table is applicable when CM01 starts initially.
System load range
0
1
2
3
Local load range
0
1
1
1
Master unit
CM01
0rps
20−112rps
52−112rps
52−120rps
Slave unit 1 CM11
0rps
0rps
52−112rps
52−120rps
Slave unit 2 CM21
0rps
0rps
0rps
31−70rps
Model 224 (Master) +
280 (Slave 2)
224 (Slave 1) +
Master unit
Slave unit 1
Slave unit 2
CM01
CM11
(CM1)
CM21
(CM1)
(CM1)
Range of the compressor operation speed relative to load is as follows. Following table is applicable when CM01 starts initially.
System load range
0
1
2
3
Local load range
0
1
1
1
Master unit
CM01
0rps
20−112rps
52−112rps
52−120rps
Slave unit 1 CM11
0rps
0rps
31−65rps
31−70rps
Slave unit 2 CM21
0rps
0rps
0rps
52−120rps
Model 224 (Master) +
224 (Slave 2)
280 (Slave 1) +