'14 • KX-SM-204
–
26
–
.;60
8) 3 outdoor units combination use (Model 850, 900, 950, 1000)
Master unit
Slave unit 1
Slave unit 2
CM01
CM11
(CM1)
CM21
(CM1)
(CM1)
Range of the compressor operation speed relative to load is as follows. Following table is applicable when CM01 starts initially.
System load range
0
1
2
3
Local load range
0
1
1
1
Master unit
CM01
0rps
íUSV
íUSV
íUSV
Slave unit 1 CM11
0rps
0rps
íUSV
íUSV
Slave unit 2 CM21
0rps
0rps
0rps
íUSV
(ii) Rotation of compressor start/stop order
1) The compressors will be changed over by determinating the start/stop order in each heat load zone.
2) In case of single use, the starting order of CM1 and CM2 will be changed over on each occasion when the out-
door unit stops.
3) In case of combination use, the starting order of CM01(CM11)
〔
CM21
〕
and CM02(CM12)
〔
CM22
〕
will be
changed over on each occation when the master unit or slave unit stops all independently.
4) In case of combination use, the starting order of master and slave units will be changed over on each occasion
when the master unit or slave unit stops all independently.
Starting order of outdoor units
0DVWHUĺ6ODYHĺ0DVWHU