'14 • KX-SM-204
-
12
-
PUSH
Demand input 2
OFF
OFF
ON
ON
PUSH PUSH
PUSH
Remote control operation
Remote control display
Air-conditioner operation/stop
Remote
Demand control
Normal
Normal
.;60
OFF
OFF
ON
ON
Demand control
Demand control
demand
demand demand demand demand demand
1st step
1st step
2nd step 3rd step 2nd step 1st step
Normal
Normal
Demand input
(CnS1,S2,G1,G2)
(CnS1,S2,G1,G2)
Valid(Open)
Invalid(Shorted)
Valid(Open)
Invalid(Shorted)
Normal
Normal
) Ending condition
When the starting conditions have been lost.
(d) Demand control from indoor unit
) Starting condition
①
When a demand ratio (“0%”, “0%”, “0%” or “0%”) has been transmitted from an indoor unit of “Peak-cut
timer” function.
②
Normal demand of Item (b) is not activated.
③
This control is performed on the RC-EXA remote control.
) Contents of control
①
Compressor’s upper limit speed is restricted according to the demand restriction rate.
②
The demand ratio controlled by the restriction rate which is transmitted from an indoor unit.
③
If the demand control rate signals are received from two or more indoor units, the control takes the lowest rate.
④
When the demand rate is other than 0%, this control is superseded by the controls of -way valve safeguard, de-
frost operation, oil return operation, oil equalized operation, pump-down operation for replacement, Start/Stop
pump-down operation and check operation.
) Ending condition
When the starting conditions have been lost.