–
–
'14 • KX-SM-204
(6) Operation and error signal output (Master unit/Slave unit)
This is the function to retrieve and display the operation and error information on the outdoor unit as a batch.. Although
indoor units also have the function to retrieve the operation and error information, this function is designed to retrieve the whole
information of each refrigeration system connected to the outdoor unit.
(a) The terminals for the operation and error outputs at the outdoor unit side are provided on the outdoor control PCB.
(b) Diagram of output relay operations
(c) The error output relay (XE) is turned ON when the error stop occurs, and is turned OFF when the error reset is done
from remote control by pressing "Check" and "Reset" button simultaneously after recovery from the error (Remote con
-
trol reset case
②
).
Before recovery from the error, if the error reset is done from remote control, XE is not turned OFF, but it will be turned
OFF automatically after the error is recovered subsequently (Remote control reset case
①
).
(d) If at least one of connected indoor units is operating, the operation output relay (XR) is turned ON. (Operation means
the state that remote control is turned ON, in which the fan operation and the thermostat OFF is included, but the error
stop is excluded.)
(e) Output relay (52XR, 52XE) of DC12V should be prepared in the field. The maximum load of relay is LY2F (Omron).
(f) The output connectors (CnH, CnY) to be connected to the relays for operation output (52XR) and for error output (52XE)
is mounted on the outdoor control PCB.
(g) If CPU goes out of control, this function becomes disable.
(h) When the automatic backup operation is effective, there is no error display for any error on the compressor stopping by
detecting its anomaly.
(7) External output
This function is used in order to operate the external option devices in conjunction with relay output of the respective opera-
tional information from outdoor unit.
However, since these models do not have dedicated output, it makes switchable by using the existing R relay in order to com-
ply with various usages.
This control is done for master unit and slave unit independently.
[External output function]
External output function of CnH can be switched by changing of [P0] of -segment display from
"0" to "5" as mentioned below.
0: Operation output [Factory default]
: Error output
·It is turned on at anomalous stop, and turned OFF when "CHECK" and "RESET" buttons on remote control are pressed si
-
multaneously after recovering from the anomaly. Even if "CHECK" and "RESET" buttons are pressed before recovering from
the anomaly, it is not turned OFF. But when recovering from the anomaly later, it is automatically turned OFF.
OFF
OFF
ON
ON
Error output 52XE
Presence of error
Outdoor LED for inspection
Normal
Normal
Error
Error
Case
②
Case
①
Remote
control reset
Case
①
Remote
control reset
Case
②
Dip switch
Reset