0
–
'14 • KX-SM-204
-
19
-
(b) 7-Segment display
Code
No.
Remarks
Contents of display
Data display
range
Minimum
unit
C00
C01
C02
C03
C04
C05
C06
C07
C08
C10
C11
C12
C13
C14
C15
C16
C18
C19
C20
C21
C22
C23
C24
C25
C26
0~130
0~130
L,-20~43
L,-25~73
L,-25~73
L,-25~73
L,-25~73
L,31~136
L,31~136
L,5~90
L,5~90
L,31~136
L,31~136
L,18~73
L,-25~73
L,-25~73
0~70
0~70
0~500
0~500
0~500
0~1500
0~1500
0~5.00
0~2.00
1Hz
1Hz
1°C
1°C
1°C
1°C
1°C
1°C
1°C
1°C
1°C
1°C
1°C
1°C
1°C
1°C
1A
1A
1 Pulse
1 Pulse
1 Pulse
10 min
10 min
0.01MPa
0.01MPa
CM2 operating frequency
Tho-A Outdoor air temp.
Tho-R1 Heat exchanger temp. 1 (Exit. Front)
Tho-R2 Heat exchanger temp. 2 (Exit. Rear)
Tho-R3 Heat exchanger temp. 3 (Entrance. Front)
Tho-R4 Heat exchanger temp. 4 (Entrance. Rear)
Tho-D1 Discharge pipe temp. (CM1)
Tho-D2 Discharge pipe temp. (CM2)
Tho-C1 Under-dome temp. (CM1)
Tho-C2 Under-dome temp. (CM2)
Tho-P1 Power transistor temp. (CM1)
Tho-P2 Power transistor temp. (CM2)
Tho-SC Sub-cooling coil temp.1
Tho-SC Sub-cooling coil temp.2
Tho-S Suction pipe temp.
CT1 Current (CM1)
CT2 Current (CM2)
EEVH1 Heating expansion valve opening angle
EEVH2 Heating expansion valve opening angle
Opening angle of EEVSC Sub-cooling coil
expansion valve
FM01 Number of rotations
FM02 Number of rotations
PSL Low pressure sensor
−
−
Ð
CM1 operating frequency
Unusual code
Pump down
Check mode
Outdoor unit setup, piping cleaning
E??
PoE, PoS
CH?, PCL?
oPE??
PSH High pressure sensor
-1
-1
C30
0,1
63H1-1
63H1-2
(63H1-R)
−
Order of 100 : 63H1-1, 2
Order of 10 : 63H1-R
(0: Close, 1: Open)